Inspection
Inspection Details
Equipment ID
9742
9742
Inspection Date
5/9/2024
5/9/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Ledden
Michael Ledden
Mechanic Name
Phillip Moise, Jr.
Phillip Moise, Jr.
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
20
20
External ID
9a252738-ea1b-4d50-b380-b999efc9578d
9a252738-ea1b-4d50-b380-b999efc9578d
Location
Red Rose Pershing LLC
5616 Pershing Ave, St. Louis, MO
Phone: (314) 728-8459
5616 Pershing Ave, St. Louis, MO
Phone: (314) 728-8459
Owner
Attn: Michelle Doyle
Red Rose Pershing LLC
5616 Pershing Ave, St. Louis, MO 63112
Phone: (314) 728-8459
Email: Michelle@bluedoorstl.com
Red Rose Pershing LLC
5616 Pershing Ave, St. Louis, MO 63112
Phone: (314) 728-8459
Email: Michelle@bluedoorstl.com
Billing
Attn: Jake Redlingshafer
Red Rose Pershing LLC
7374 Elm Ave, Maplewood, MO 63143
Phone: (314) 728-8459
Email: Madison@bluedoorstl.com
Red Rose Pershing LLC
7374 Elm Ave, Maplewood, MO 63143
Phone: (314) 728-8459
Email: Madison@bluedoorstl.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | A fire extinguisher shall be provided in the elevator machine room. | 9/1/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The emergency lights shall be operational. | 5/21/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | The alarm bell shall be operational. | 5/21/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display the current state operating certificate in the elevator machine room. | 9/1/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency lighting shall be operational. | 5/9/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency telephone shall be operational. | 5/9/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Pipes conveying liquids in the machine room shall be guarded or guttered. | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 5/9/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Pipes conveying liquids in the machine room shall be guarded or guttered. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 5/8/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | No | Pipes conveying liquids in the machine room shall be guarded or guttered. This is a multi-year violation that has not been corrected. Re-Inspection required. | 5/9/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | Yes | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. This is a multi-year violation that has not been corrected. Re-Inspection required. | 5/9/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. This is a multi-year violation that has not been corrected and is a life safety item. Elevator will be red tagged if not corrected immediately. | 5/9/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Light bulbs in the elevator cab shall be guarded to prevent accident contact and breakage. Additionally, some of the bulbs need to be replaced. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Ceiling tiles are missing inside the car enclosure. Replace missing tiles. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | No | Pipes conveying liquids in the machine room shall be guarded or guttered. This is a multi-year violation that has not been corrected. Re-Inspection required. | 4/30/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | Yes | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. This is a multi-year violation that has not been corrected. Re-Inspection required. | 4/30/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Drop ceiling and lights in cab shall be repaired. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | No | Pipes conveying liquids in the machine room shall be guarded or guttered. This is a multi-year violation. Re-Inspection now required. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency lighting shall work. 1 of 2 lamps not working. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Car door electric eye not working. Repair/replace. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The machine room door shall be self-closing, self-locking and shall be operable from the interior space without the use of a key. | |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Fire service testing must be documented monthly. | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Light bulbs in the elevator cab shall be guarded (ceiling grid tiles) to prevent accident contact and breakage. Additionally, some of the bulbs need to be replaced. This is a multi-year violation. Failure to correct violation may result in elevator being red tagged until completed. |