Inspection
Inspection Details
Equipment ID
11564
11564
Inspection Date
5/6/2024
5/6/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Thomas Jimas
Thomas Jimas
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
23
23
External ID
0285e3bd-7f8e-4e9c-be2e-66df9ff3bf1c
0285e3bd-7f8e-4e9c-be2e-66df9ff3bf1c
Location
8th Street Bank
721 Locust St, St. Louis, MO
Phone: (314) 418-1933
721 Locust St, St. Louis, MO
Phone: (314) 418-1933
Owner
Attn: Amy Borgstede
US Bank c/o Cushman & Wakefield
1 US Bank Plz, Ste 200, St. Louis, MO 63101
Phone: (314) 328-7060
Alt Phone: (314) 202-1319
Email: Amy.Borgstede@cushwake.com
US Bank c/o Cushman & Wakefield
1 US Bank Plz, Ste 200, St. Louis, MO 63101
Phone: (314) 328-7060
Alt Phone: (314) 202-1319
Email: Amy.Borgstede@cushwake.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall work. | 9/25/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Fire service testing must be documented monthly. | 9/25/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2 On-Site Documentation | No | No | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. | 9/25/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/25/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Cartop shall be kept free of excess dirt & debris. | 9/25/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Repair machine room smoke detector, damaged and hanging by its wiring. | 9/25/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Fire service testing must be documented monthly. Not verified at time of phone reinspection, owner to self-certify. | 10/7/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2 On-Site Documentation | No | No | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. Not verified at time of phone reinspection, owner to self-certify. | 10/7/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 10/7/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Cartop shall be kept free of excess dirt & debris. Not verified at time of phone reinspection, owner to self-certify. | 10/7/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Repair machine room smoke detector, damaged and hanging by its wiring. Not verified at time of phone reinspection, owner to self-certify. | 10/7/2025 |