Inspection
Inspection Details
Equipment ID
25965
25965
Inspection Date
5/8/2024
5/8/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Sean Carmody
Sean Carmody
Mechanic Name
Jason Bock
Jason Bock
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
24
24
External ID
5faeac88-c4fa-48e3-838e-2b3a18f6d741
5faeac88-c4fa-48e3-838e-2b3a18f6d741
Location
Hoffman Lofts
700-702 N 2nd St, St. Louis, MO
Phone: (000) 000-0000
700-702 N 2nd St, St. Louis, MO
Phone: (000) 000-0000
Owner
Attn: Hoffman Lofts, LLC
Hoffman Lofts, LLC
701 N 1st St, Ste 102, St. Louis, MO 63102
Phone: (314) 260-9266
Email: Bminges@advantesgrp.com
Hoffman Lofts, LLC
701 N 1st St, Ste 102, St. Louis, MO 63102
Phone: (314) 260-9266
Email: Bminges@advantesgrp.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (A) - Hoistways | (A)3 | No | Yes | Hoistway door closers not working, needs repair. Red tagged, removed from service. Re-inspection required | 7/6/2022 |
| MO Minimum : Elevators | (A) - Hoistways | (A)3 | No | Yes | Replace missing pick-up rollers @ top floor hoistway door. Red tagged, removed from service. Re-inspection required | 7/6/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | Yes | Provide working elevator pit lights. Red tagged & removed from service. Re-inspection required | 7/6/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | Yes | Generator in machine room shaking due to internal malfunction and won't run car at rated speed, needs repaired. Red tagged, Removed from service. Re-inspection required | 7/6/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A copy of the MCP shall be kept in the machine room for each elevator | 5/3/2023 |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | Yes | Yes | Test car safeties, rated speed, rated load. Red tagged, removed from service. Re-inspection required | 7/6/2022 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Test fire service. Red tagged, removed from service. Re-inspection required | 7/6/2022 |
| MO Minimum : Elevators | (A) - Hoistways | (A)3 | No | No | Hoistway door closers not working, needs repair or replaced. | 5/2/2023 |
| MO Minimum : Elevators | (A) - Hoistways | (A)3 | No | No | Replace missing pickup rollers at top hoistway door | 5/2/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Provide pit light that works | 5/2/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A copy of the MCP shall be kept in the machine room for each elevator. | 5/2/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not working. Re-inspection required | 1/29/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Smoke detector system not in place, provide same and test with elevator system. Re-inspection required. | 1/29/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 5/3/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | 5/3/2024 |