Inspection
Inspection Details
Equipment ID
7416
7416
Inspection Date
3/6/2024
3/6/2024
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Thomas Suedkamp
Thomas Suedkamp
Relief Valve Pressure
Na
Na
Slide
11”
11”
Governor Rope Pull
85/560
85/560
Door Closing Force
20
20
External ID
9986b8e5-26fa-4396-9f3c-585868fa0e2d
9986b8e5-26fa-4396-9f3c-585868fa0e2d
Location
Le Meridien Clayton
7730 Bonhomme Ave, Clayton, MO
Phone: (314) 863-0400
7730 Bonhomme Ave, Clayton, MO
Phone: (314) 863-0400
Owner
Attn: Silverwest-I Clayton, LLC
Silverwest-I Clayton, LLC
101 University Blvd, Ste 200, Denver, CO 80206
Phone: (314) 719-4328 Ext: 7126
Email: arta.dora@lemeridienclayton.com
Silverwest-I Clayton, LLC
101 University Blvd, Ste 200, Denver, CO 80206
Phone: (314) 719-4328 Ext: 7126
Email: arta.dora@lemeridienclayton.com
Billing
Attn: Silverwest-I Clayton, LLC
Silverwest-I Clayton, LLC
101 University Blvd, Ste 200, Denver, CO 80206
Phone: (314) 863-0400
Email: ron.blake@lemeridienclayton.com
Silverwest-I Clayton, LLC
101 University Blvd, Ste 200, Denver, CO 80206
Phone: (314) 863-0400
Email: ron.blake@lemeridienclayton.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.8 - Top emergency exit | 8.11.2.1.3(l) | No | No | Emergency exit shall be operable, remove temporary weights from top of hatch. | 4/14/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 3/2/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.6 Sump Pump Covers | No | No | Pit sump pump hole is not covered. | 4/14/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.28 - Counterweight and counterweight buffer | 8.11.2.1.3(m) | No | No | Counterweights are compressing buffer in pit when car is at top landing. Shorten ropes to provide minimum runby of 6" | 4/14/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | No maintenance records on site. | 4/14/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.8 - Top emergency exit | 8.11.2.1.3(l) | No | No | Emergency hatch shall be operable. Remove temporary weights from top of hatch. | 4/14/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Written maintenance control program shall be provided on site. | 4/14/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.6 Sump Pump Covers | No | No | Sump pump hole shall be covered. | 4/14/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.28 - Counterweight and counterweight buffer | 8.11.2.1.3(m) | No | No | Counterweights are compressing buffer in pit when car is at the top landing. Hoist ropes need to be shortened to get minimum runby of 6". | 4/14/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | No maintenance control program in the machine room | 4/14/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Test incomplete. Car top still needs to be inspected | 10/12/2021 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Provide testing on emergency power. | 8/9/2024 |
| A17.1-2016 : Elevators | 4.12 - Standby power selection switch | 8.6.4.19.7 (Re-Inspection) | Yes | No | Provide testing. | 8/9/2024 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)6 | Yes | No | Re-install buffer switches on car and counterweights. | 10/14/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean oil off of pit floor. | 10/14/2025 |