Inspection
Inspection Details
Equipment ID
3838
3838
Inspection Date
5/28/2024
5/28/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Dixon Liljegren
Dixon Liljegren
Mechanic Name
Michael Bales
Michael Bales
Relief Valve Pressure
480
480
Slide
0
0
Governor Rope Pull
0
0
Door Closing Force
22
22
External ID
7c6c9bd6-fe85-48db-b402-6acdb6e51b95
7c6c9bd6-fe85-48db-b402-6acdb6e51b95
Location
Prairie Branch Elementary
2100 S Dillingham Rd, Grain Valley, MO
Phone: (816) 847-5070
2100 S Dillingham Rd, Grain Valley, MO
Phone: (816) 847-5070
Owner
Attn: Jessica Gleason
Grain Valley R-5 School District
PO Box 304, Grain Valley, MO 64029
Phone: (816) 847-5006 Ext: 1019
Email: jgleason@gvr5.net
Grain Valley R-5 School District
PO Box 304, Grain Valley, MO 64029
Phone: (816) 847-5006 Ext: 1019
Email: jgleason@gvr5.net
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | no sump pump cover | 9/16/2022 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 102 | Yes | No | sump pump pluged into GFI outlet no seperate non gfi for sump pump to plug into | 5/11/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | when car lighting turned off phone went dead. need standby power to phone | 5/11/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light not working. | 9/16/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | Provide non combustable cover for sump pump in pit. | 9/16/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | Provide a non combustable cover for sump pump in pit. | 9/16/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit lighting not working. | 9/16/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Oil in pit. Clean pit and remove old oil dry from floor. | 9/16/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | No | No | Jack packings leaking, repack. | 5/27/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working, alarm bell ok. | 5/28/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency lights not working. | 5/28/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Remove all non elevator related items from machine room, and keep clear. | 5/27/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | No | No | Jack packings leaking, repair. | 5/27/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working, alarm bell ok. | 7/19/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light not working. | 5/27/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not connecting. | 5/29/2025 |