Inspection
Inspection Details
Equipment ID
2763
2763
Inspection Date
5/15/2024
5/15/2024
Inspection Type
Reinspection
Reinspection
Inspector Name
Daniel Swett
Daniel Swett
Mechanic Name
Thomas Suedkamp
Thomas Suedkamp
Relief Valve Pressure
N/A
N/A
Slide
22
22
Governor Rope Pull
70/390
70/390
Door Closing Force
N/A
N/A
External ID
67ae2a9d-3dd8-40d9-9273-64af9f76a2fd
67ae2a9d-3dd8-40d9-9273-64af9f76a2fd
Location
McDonnell Science Bldg
4566 Scott Ave, St. Louis, MO
Phone: (314) 362-2907
4566 Scott Ave, St. Louis, MO
Phone: (314) 362-2907
Owner
Attn: Matt Dissett
WUSM
660 S Euclid Ave, CB 8080, St. Louis, MO 63110
Phone: (314) 273-3124
Fax: (314) 747-0727
Email: mdissett@wustl.edu
WUSM
660 S Euclid Ave, CB 8080, St. Louis, MO 63110
Phone: (314) 273-3124
Fax: (314) 747-0727
Email: mdissett@wustl.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | Water in pit (1”) | 5/1/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Emer Power not tested. | 4/28/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.42 Seismic (Earthquake protection) | 8.4.10 | No | No | Ring and string operation not working. | 5/1/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm not working on normal power. | 4/28/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.3 Provide Auxiliary Lighting | Yes | No | Emergency lights not working. | 4/28/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.12 - Standby power selection switch | 2.27.2 | No | No | Standby power operation has not been tested. | 5/1/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Standing water in pit. | 5/1/2026 |
| A17.1-2016 : Elevators | 3.23 - Suspension Means | 8.6.4.1 | No | No | Suspension ropes not equally tensioned. | 5/1/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | No Category 5 tests performed/witnessed. | 5/15/2024 |
| A17.1-2016 : Elevators | 3.23 - Suspension Means | 8.6.4.1 | No | No | Suspension ropes not equally tensioned. | 5/1/2026 |
| A17.1-2016 : Elevators | 3.23 - Suspension Means | 8.11.3.1.3(x) | Yes | No | Suspension rope undersized. | 4/14/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2.3 (Elevator Emergency Power Illuminated Signal) | No | No | Emergency power indicator jewel in hall not working. | 5/1/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2.3 (Elevator Emergency Power Illuminated Signal) | No | No | Emergency power indicator jewel in hall not working. | 5/6/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Means of two way communication inoperable and shall be repaired or replaced. |