Inspection
Inspection Details
Equipment ID
12185
12185
Inspection Date
5/22/2024
5/22/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Sean Carmody
Sean Carmody
Mechanic Name
Phillip Moise, Jr.
Phillip Moise, Jr.
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
16
16
External ID
d5aa102d-9b6e-446d-a3af-6efddb0a7eea
d5aa102d-9b6e-446d-a3af-6efddb0a7eea
Location
Hillside Manor
1265 McLaran Ave, St. Louis, MO
Phone: (314) 388-5926
1265 McLaran Ave, St. Louis, MO
Phone: (314) 388-5926
Owner
Attn: Administrator
Hillside Rehab and Healthcare Center
1265 McLaran Ave, St. Louis, MO 63147
Phone: (314) 388-4121 Ext: 122
Email: rjones@hillsiderehabhc.com
Hillside Rehab and Healthcare Center
1265 McLaran Ave, St. Louis, MO 63147
Phone: (314) 388-4121 Ext: 122
Email: rjones@hillsiderehabhc.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | x | Replace the hoist ropes. | 10/8/2019 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | x | The car door restrictor shall work. | 10/8/2019 | |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | x | Phase 2 fire service shall work. Phase 2 fire service shall be tested. | 10/8/2019 |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)7 | x | x | Full load test tags where not on equipment. Attach tags or Cat 5 test shall be performed. | 5/28/2021 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | x | When key is engaged for Phase I fire service, elevator does not return to the designated floor. Red tagged. | 5/28/2021 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | x | Phase II fire service does not operate. Red tagged. | 5/28/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Jumpers in fire service panel must be removed. | 4/27/2022 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | Electrical wiring for the machine room light must be ran in an enclosed circuit, raceway and comply with NFPA 70. | 4/27/2022 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | Electrical prints shall be provided in the machine room. | 4/27/2022 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | Non-elevator related material needs to be removed from machine room. | 8/22/2024 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | Traveling cable is not in protective raceway in machine room. | 8/22/2024 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | Covers are missing in machine room raceway. | 8/22/2024 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | The top of the car is dirty. Clean the car top. | 8/22/2024 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | The hoistway is dirty. Clean the hoistway. | 8/22/2024 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. |