Inspection
Inspection Details
Equipment ID
11959
11959
Inspection Date
6/4/2024
6/4/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Timothy Trout
Timothy Trout
Mechanic Name
Steve Wiseman
Steve Wiseman
Relief Valve Pressure
480
480
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
26
26
External ID
86df9d7c-f26e-4a8b-be21-52452018a8d2
86df9d7c-f26e-4a8b-be21-52452018a8d2
Location
Quality Inn W 76
1835 W 76 Country Blvd, Branson, MO
Phone: (417) 336-1600
1835 W 76 Country Blvd, Branson, MO
Phone: (417) 336-1600
Owner
Attn: Krishna Patel
Krishna Patel
1835 W 76 Country Blvd, Branson, MO 65616
Phone: (417) 336-1600
Email: gm@qualityinnbransoncentral.com
Krishna Patel
1835 W 76 Country Blvd, Branson, MO 65616
Phone: (417) 336-1600
Email: gm@qualityinnbransoncentral.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Replace the missing door closer on the machine room It needs to be self closing self latching. | 8/29/2018 |
| conversion | conversion | n/a | No | No | Remove all the stored materials from the machine room | 8/29/2018 |
| conversion | conversion | n/a | No | No | Replace all the electrical wiring and devices located below pit access level with NEMA 4 rated equipment,wet location, that has been under water for a period of time . | 8/29/2018 |
| conversion | conversion | n/a | No | No | Remove the 3 foot plus water from the pit, you have to maintain a dry pit. | 8/29/2018 |
| conversion | conversion | n/a | No | No | Provide an approved pit stop switch | 8/29/2018 |
| conversion | conversion | n/a | No | No | Replace the stop switch in the pit for an approved stop/ run switch per code. | 8/29/2018 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1001.2(b)(5) | No | No | Clean out the machine room as it is not a storage room for your equipment and materials. | 8/19/2019 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | Have the fire extinguisher re-certified | 8/19/2019 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operating certificate in the machine room | 8/19/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Have the emergency phone repaired as there is no dial tone. | 9/23/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Replace the bad alarm battery | 9/17/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Replace the burnt out pit light | 12/3/2021 |
| A17.1-1996 : Elevators | 3.16 - Traveling cables and junction boxes | 102.1 | No | No | The traveling cable is broken and won't let the car run on automatic. The inspection was abborted | 9/23/2022 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 101.5b | No | No | Repair the HVAC unit in the machine room. | 1/8/2024 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 101.5b | No | No | Repair the non working AC unit in the machine room | 8/16/2024 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | REPAIR THE EMERGENCY PHONE AS THE INCOMIN LINE HAS NO VOLTAGE ON IT |