Inspection
Inspection Details
Equipment ID
15298
15298
Inspection Date
5/30/2024
5/30/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Bradley Rasnake
Bradley Rasnake
Mechanic Name
Tom Worsham
Tom Worsham
Relief Valve Pressure
440
440
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
25
25
External ID
2f4ccf1f-f273-4f2f-86a1-55ce527adc34
2f4ccf1f-f273-4f2f-86a1-55ce527adc34
Location
SOHA Lofts LLC
4650 Hampton Ave, St. Louis, MO
Phone: (314) 429-2919
4650 Hampton Ave, St. Louis, MO
Phone: (314) 429-2919
Owner
Attn: SOHA Lofts LLC
SOHA Lofts LLC
10707 Midwest Industrial Blvd, St. Louis, MO 63132
Phone: (314) 429-2919
SOHA Lofts LLC
10707 Midwest Industrial Blvd, St. Louis, MO 63132
Phone: (314) 429-2919
Billing
Attn: Matt Salviccio
XL Building Products c/o SOHA Lofts LLC
10707 Midwest Industrial Blvd, St. Louis, MO 63132
Phone: (314) 429-2919
Email: sohalofts@gmail.com
XL Building Products c/o SOHA Lofts LLC
10707 Midwest Industrial Blvd, St. Louis, MO 63132
Phone: (314) 429-2919
Email: sohalofts@gmail.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | No | No | Emergency operation of signaling devices, lighting,communication and ventilation, shall be maintained. Emergency lighting isn't functioning. Ref: 8.6.4.15 | 7/31/2018 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1004.2(a)(6) (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light and alarm bell do not work. | 6/29/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1004.2(a)(6) (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 6/29/2021 |
| A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | Yes | No | Valve is unsealed. Perform OSV test, tag and seal upon completion. | 6/14/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light and alarm bell inoperative. Repair | 6/14/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) | No | No | Provide on-site, up to date wiring diagrams. | |
| A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | Yes | No | OSV is not sealed, must be Cat 5 tested. Re-inspection required | 6/8/2023 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone line does not call out & emergency light does not work. Re-inspection required | 6/8/2023 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. 2.27.1.1.1 | 5/30/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | The machine room shall not be used for storage, only elevator equipment shall be stored in elevator machine room | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current operating certificate shall be displayed in the machine room | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | OSV is not sealed, must be Cat 5 tested. Re-inspection required |