Inspection
Inspection Details
Equipment ID
15296
15296
Inspection Date
6/6/2024
6/6/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Thomas McGrath
Thomas McGrath
Mechanic Name
Jarod Watson
Jarod Watson
Relief Valve Pressure
350
350
Slide
NA
NA
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
11
11
External ID
9f46eaf1-9588-43a6-b4ba-674db43b48cf
9f46eaf1-9588-43a6-b4ba-674db43b48cf
Location
Staybridge Inn & Suites
1155 Technology Dr, O'Fallon, MO
Phone: (636) 300-0999
1155 Technology Dr, O'Fallon, MO
Phone: (636) 300-0999
Owner
Attn: Mina Patel
1155 Technology LLC
2128 William St #161, Cape Girardeau, MO 63703
Phone: (561) 568-0244
Email: Mina.patel@appleig.com
1155 Technology LLC
2128 William St #161, Cape Girardeau, MO 63703
Phone: (561) 568-0244
Email: Mina.patel@appleig.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.7 - Car door or gate | 1001.2(a)(7) | No | No | Correct source of noise from car door. | 6/4/2019 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 6/21/2021 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 6/21/2021 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 6/21/2021 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | The in car emergency lighting shall be operational. | 6/21/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency alarm bell shall be operational on auxiliary power. | 6/21/2021 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | Yes | No | The emergency lowering device (ERU) shall be operational. | 6/21/2021 |
| A17.1-1996 : Elevators | 2.11 - Disconnecting Means and Control | 210.4 | No | No | Where an additional power source is connected to the load side of the disconnecting means, the disconnecting means required in Section 620-51 shall be provided with an auxiliary contact that is positively opened mechanically and the opening shall not be solely dependent on springs. This contact shall cause the additional power source to be disconnected from its load when the disconnecting means is in the open position. | 6/21/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Remove all non elevator storage from the machine room | 5/23/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service testing and document on log in machine room | 5/23/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Document routine maintenance in the maintenance control program | 5/23/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service and document on log in machine room | 6/28/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Service fire extinguisher in the machine room | 6/28/2024 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | POST CURRENT STATE CERTIFICATE IN THE MACHINE ROOM | 6/13/2025 |
| A17.1-2016 : Elevators | 6.1 - Operation of elevators under fire and other emergency conditions (A17.1b-1973 through A17.1b-1980) | 8.6.11.1 Firefighters’ Emergency Operation | No | No | PERFORM MONTHLY FIRE SERVICE TEST AND DOCUMENT ON THE LOG POSTED IN THE MACHINE ROOM | 6/13/2025 |
| A17.1-1996 : Elevators | 1.4 - Sills and car floor | 110.11a | No | No | Secure carpet at 2nd floor elevator entrance. Tripping hazard. | 6/13/2025 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Repair emergency battery lowering unit. | 9/19/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency lighting in the elevator cab is inoperative and shall be repared to provide the required standby illumination. |