Inspection
Inspection Details
Equipment ID
681
681
Inspection Date
11/8/2018
11/8/2018
Inspection Type
Reinspection
Reinspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
9a55d90b-11ce-4bea-9c5f-599e22891ff0
9a55d90b-11ce-4bea-9c5f-599e22891ff0
Location
Tallin Building
8350 DELCREST DR, SAINT LOUIS, MO
8350 DELCREST DR, SAINT LOUIS, MO
Owner
Council Apartments II
8350 DELCREST DR, SAINT LOUIS, MO 63124-2166
8350 DELCREST DR, SAINT LOUIS, MO 63124-2166
Billing
Attn: Crown Center
8350 DELCREST DR, SAINT LOUIS, MO 63124-2166
8350 DELCREST DR, SAINT LOUIS, MO 63124-2166
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | Emergency phone now working. | 11/8/2018 | |
MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | Repair pit light. | 1/20/2021 | ||
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not work. | 9/11/2019 | |
A17.1-1996 : Elevators | 3.28 - Counterweight and counterweight buffer | 202 | x | The left bottom counterweight guide roller needs to be replaced. | 9/11/2019 | |
A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 1001.2(b)(3) Inspection code | A machine room light fixture was not operational on the day of inspection. Repair light fixture for proper illumination for maintenance and emergency personnel. | |||
A17.1-1996 : Elevators | 3.28 - Counterweight and counterweight buffer | 1001.2(c)(13) | There is a bottom guide roller on the counterweight that has deteriorated and shall be replaced. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of 8.6.The MCP shall include but not limited to examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) | Unusual testing procedures not outlined in A17.2 shall be present and accessible according to this code section. These include but not limited to procedures for tests, periodic inspections, maintenance, replacements, adjustments, and repairs for traction-loss detection means, broken-suspension-member detection means, residual-strength detection means, and related circuits. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. | |||
A17.1-1996 : Elevators | 1.8 - Door closing force | 1001.2(a)(8) | x | The elevator car door closing force is over the maximum allowable force of 30lbs. Readjust door closing force to be less than 30lbs. Reinspection required. | 6/20/2022 |