Inspection
Inspection Details
Equipment ID
8088
8088
Inspection Date
5/31/2024
5/31/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Phillip Moise, Jr.
Phillip Moise, Jr.
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
88dd0025-f377-44f1-8c13-8f73a1b8cd02
88dd0025-f377-44f1-8c13-8f73a1b8cd02
Location
The Fremont
4066 Lindell Blvd, St. Louis, MO
Phone: (314) 367-1106
4066 Lindell Blvd, St. Louis, MO
Phone: (314) 367-1106
Owner
Attn: Karen Karabell
S.F. Shannon Real Estate,LLC
PO Box 4675, St. Louis, MO 63108
Phone: (314) 367-1106
Email: info@sfshannon.com
S.F. Shannon Real Estate,LLC
PO Box 4675, St. Louis, MO 63108
Phone: (314) 367-1106
Email: info@sfshannon.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Shorten the hoist ropes. | 8/13/2018 |
| conversion | conversion | n/a | No | No | Remove all non-elevator related materials from the elevator machine room. | 8/13/2018 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Car emergency light shall have 2 working bulbs. | 7/15/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Car emergency light shall be guarded to prevent accidental contact or breakage. | 7/15/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)3 | No | No | Existing emergency exit is not code compliant and shall be replaced. | 7/15/2019 |
| MO Minimum : Elevators | (A) - Hoistways | (A)1 | No | No | Hoistway doors on floors 1,2,3,5, & 6 do not have code compliant glass and shall be repaired or replaced as needed. | 7/15/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean. Clean the pit. | 8/25/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | A current tested ABC type fire extinguisher shall be provided in the elevator machine room. | 8/25/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 8/1/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | 8/1/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit shall be kept clean. | 8/12/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Car top shall be kept clean. | 8/12/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency two-way communications not working. | 7/10/2025 |
| MO Minimum : Elevators | (A) - Hoistways | (A)10 | Yes | No | Install pull chain at bottom floor for pit access. | 7/10/2025 |