Inspection
Inspection Details
Equipment ID
11794
11794
Inspection Date
6/10/2024
6/10/2024
Inspection Type
Alteration
Alteration
Inspector Name
Thomas Krug
Thomas Krug
Mechanic Name
Jonathan Harrison
Jonathan Harrison
Relief Valve Pressure
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
na
na
External ID
6d5df005-e604-490e-ae19-b9afa94319cd
6d5df005-e604-490e-ae19-b9afa94319cd
Location
Bernard Care Center
4335 W Pine Blvd, St. Louis, MO
Phone: (314) 371-0200
4335 W Pine Blvd, St. Louis, MO
Phone: (314) 371-0200
Owner
Attn: Bernard Care Center
Bernard Care Center
4335 W Pine Blvd, St. Louis, MO 63108
Phone: (000) 000-0000
Bernard Care Center
4335 W Pine Blvd, St. Louis, MO 63108
Phone: (000) 000-0000
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Alarm bell shall work | 4/26/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Phone should call 24 hrs. monitored number, not a recording | 4/26/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Repair inoperable emergency phone | 8/10/2018 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | No storage in machine room except items related to elevator. | 10/1/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Repair leaking pipes and protect equipment from water and moisture. | 10/1/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light does not work. | 10/1/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Repair leaking pipe in machine room and protect equipment from water and moisture. | 10/1/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | No maintenance records on site. | 10/1/2020 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Governor rope is severely rouged and needs to be replaced. Re-inspection required | 4/8/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Cat 5 test is incomplete. Need to perform the following tests: check governor rope pull through and pull out force. Check tripping speed of car overspeed governor, test car safeties at rated speed with rated load. Test machine brake with 125% of rated load. Re-inspection required | 4/8/2024 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Governor rope is severely rouged, needs to be replaced. Re-inspection required | 6/10/2024 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)1(A) | No | No | Install rope data tag on governor rope | 6/10/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 6/10/2024 |