Inspection
Inspection Details
Equipment ID
19000
19000
Inspection Date
6/11/2024
6/11/2024
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Michael Wright
Michael Wright
Mechanic Name
Rodney Clay
Rodney Clay
Relief Valve Pressure
N/A
N/A
Slide
need
need
Governor Rope Pull
500
500
Door Closing Force
24
24
External ID
bae79675-f4af-4343-b873-a5ea1da1528b
bae79675-f4af-4343-b873-a5ea1da1528b
Location
Iatan Station
20256 State Rte 45 N, Weston, MO
Phone: (816) 386-2047
Email: donald.hughes@evergy.com
20256 State Rte 45 N, Weston, MO
Phone: (816) 386-2047
Email: donald.hughes@evergy.com
Owner
Attn: Steven Thomas
KC Power & Light
1201 Walnut, Kansas City, MO 64141
Phone: (000) 000-0000
Email: steven.d.thomas@evergy.com
KC Power & Light
1201 Walnut, Kansas City, MO 64141
Phone: (000) 000-0000
Email: steven.d.thomas@evergy.com
Billing
Attn: Kevin Cook
Iatan Power Plant
20250 State Rte 45 N, Weston, MO 64098
Phone: (816) 640-3675
Email: kevin.cook@evergy.com
Iatan Power Plant
20250 State Rte 45 N, Weston, MO 64098
Phone: (816) 640-3675
Email: kevin.cook@evergy.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Repair pit light. m Pit light does not illuminate. | 1/9/2019 |
| conversion | conversion | n/a | No | No | Emergency phone inside elavator does not operate. | 1/9/2019 |
| conversion | conversion | n/a | No | No | Need to install light switch near machine room access door to operate machine room light fixture. Machine light does not illuminate. | 1/9/2019 |
| conversion | conversion | n/a | No | No | Remove standing water from pit. Summp pump not operating. | 1/9/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone does not operate | 5/11/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not call out | 5/16/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Test and log firefighter operation monthly | 3/4/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Post emergency evacuation of passengers procedure in machine room | 3/4/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) | No | No | Provide firefighter operation cabinet on car operating panel | 5/16/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) | Yes | No | Provide firefighter cabinet on car operating panel | 5/23/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.2 - Car top light and outlet | 8.11.2.1.3(b) | No | No | Top of car light does not illuminate | 8/5/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 8.11.2.1.2(f) | No | No | Machine room air conditioner does not operate. | 8/5/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.4 Access to Pit | Yes | No | Replace pit ladder. Existing ladder is not usable due to corrosion from water damage. | 5/23/2023 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | No MCP in machine room | 8/5/2025 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(a)(1) | No | No | Maintenance records not up to date. | 8/5/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Current state operating certificate not displayed | 8/5/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.4 Access to Pit | Yes | No | replace defective pit ladder. | 9/6/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.9 - Guarding of exposed auxiliary equipment | 2.10.1 | No | No | hoist ropes need to be guarded to machine room floor where the ropes extend past the base of the driving machine | 8/5/2025 |
| A17.1-2016 : Elevators | 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection | 8.6.4.19.11 Ascending Overspeed Protection, Unintended Movement Devices, and Emg Brake | Yes | No | Emergency brake is not working properly | 12/3/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair the emergency phone. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Repair the machine room lighting. | 8/5/2025 |