Inspection
Inspection Details
Equipment ID
15027
15027
Inspection Date
6/11/2024
6/11/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Wright
Michael Wright
Mechanic Name
Rodney Clay
Rodney Clay
Relief Valve Pressure
N/A
N/A
Slide
NA
NA
Governor Rope Pull
N/A
N/A
Door Closing Force
24
24
External ID
bb9573f9-e929-46cd-ae17-264b931e7b4a
bb9573f9-e929-46cd-ae17-264b931e7b4a
Location
Iatan Power Plant
20250 State Rte 45 N, Weston, MO
Phone: (816) 640-3661
Alt Phone: (816) 640-3661
Email: lynette.hurst@evergy.com
20250 State Rte 45 N, Weston, MO
Phone: (816) 640-3661
Alt Phone: (816) 640-3661
Email: lynette.hurst@evergy.com
Owner
Attn: Steven Thomas
KC Power & Light
1201 Walnut, Kansas City, MO 64141
Phone: (000) 000-0000
Email: steven.d.thomas@evergy.com
KC Power & Light
1201 Walnut, Kansas City, MO 64141
Phone: (000) 000-0000
Email: steven.d.thomas@evergy.com
Billing
Attn: Kevin Cook
Iatan Power Plant
20250 State Rte 45 N, Weston, MO 64098
Phone: (816) 640-3675
Email: kevin.cook@evergy.com
Iatan Power Plant
20250 State Rte 45 N, Weston, MO 64098
Phone: (816) 640-3675
Email: kevin.cook@evergy.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Remove standing water on machine room floor. AC unit in machine room leaking water onto floor. | 1/9/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 8.11.2.1.2(o) | Yes | No | Provide means for ascending car and unintended movement protection. Existing rope gripper does not function correctly. | 4/18/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | emg. lt. an bell not working phone works but is the wrong kind | 5/16/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | pit covered in water | 1/1/2024 |
| A17.1-2016 : Elevators | 4.5 - Access to Hoistway | 8.6.4.14 Hoistway Access Switches | No | No | hoistway access sws. not working | 1/1/2024 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2 On-Site Documentation | No | No | incomplete MCP | 1/1/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency bell does not operate | 5/24/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | Emergency light does not illuminate | 5/24/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.8 Switch Keys (Re-Inspection) | Yes | No | All elevators in the same building shall have firefighter keyswitches operated by the same key | 5/24/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.12 - Controller Wiring, Fuses, Grounding, Etc. | 8.6.1.6.3 | No | No | Interior of controller and its components need to be cleaned of coal dust | 1/1/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | No | No | Layer of coal dust covering entire machine room and equipment needs to be removed | 1/1/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Current state operating certificate not displayed | 1/1/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.5 - Access to Hoistway | 8.6.4.14 Hoistway Access Switches | No | No | hoistway access switches do not function. | 1/1/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | No | No | machine room air conditioner does not work | 1/1/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) | Yes | No | car firefighter operation panel needs to have a lockable cover | 9/6/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | phone button on car operating panel does not activate the phone | 9/6/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate | 1/24/2024 |