Inspection
Inspection Details
Equipment ID
18997
18997
Inspection Date
6/11/2024
6/11/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Wright
Michael Wright
Mechanic Name
Rodney Clay
Rodney Clay
Relief Valve Pressure
N/A
N/A
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
24
24
External ID
ab3fc7c4-f801-44fc-8873-ed0ec643823b
ab3fc7c4-f801-44fc-8873-ed0ec643823b
Location
Iatan Station
20256 State Rte 45 N, Weston, MO
Phone: (816) 386-2047
Email: donald.hughes@evergy.com
20256 State Rte 45 N, Weston, MO
Phone: (816) 386-2047
Email: donald.hughes@evergy.com
Owner
Attn: Steven Thomas
KC Power & Light
1201 Walnut, Kansas City, MO 64141
Phone: (000) 000-0000
Email: steven.d.thomas@evergy.com
KC Power & Light
1201 Walnut, Kansas City, MO 64141
Phone: (000) 000-0000
Email: steven.d.thomas@evergy.com
Billing
Attn: Kevin Cook
Iatan Power Plant
20250 State Rte 45 N, Weston, MO 64098
Phone: (816) 640-3675
Email: kevin.cook@evergy.com
Iatan Power Plant
20250 State Rte 45 N, Weston, MO 64098
Phone: (816) 640-3675
Email: kevin.cook@evergy.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.14 - Code data plate | 8.9 | No | No | Provide code data plate and display on disconnect or controller. | 9/16/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | No | No | Machine room light fixture is extremly dim. Need to provide a minimum of 10 ft candles of illumination at machine room floor. | 8/15/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.14 - Code data plate | 8.9 | No | No | Need to provide code data plate and display on disconnect or controller. | 8/15/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not call out. | 5/13/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Test and log firefighter operation monthly | 3/4/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Post emergency evacuation of passengers procedure in machine room | 3/4/2023 |
| A17.1-2016 : Elevators | 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection | 8.6.4.20.11 (Re-Inspection) | Yes | No | Provide emergency brake for ascending car and unintended motion protection. | 5/13/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) | No | No | Provide firefighter cabinet on car operating panel | 5/13/2022 |
| A17.1-2016 : Elevators | 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection | 8.6.4.20.11 (Re-Inspection) | Yes | No | Provide emergency brake for ascending car and unintended motion protection | 5/22/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) | Yes | No | Provide firefighter cabinet on car operating panel | 5/22/2023 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(a)(1) | No | No | Maintenance record log not up to date | 9/16/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Current state operating certificate not displayed | 9/16/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Repair the pit light. | 8/5/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove the water from the pit. | 8/5/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair the emergency phone. | 4/30/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Provide machine room lighting. | 8/5/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove the water from the pit | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair the emergency phone |