Inspection
Inspection Details
Equipment ID
12634
12634
Inspection Date
6/18/2024
6/18/2024
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
Na
Na
Slide
12
12
Governor Rope Pull
90/500
90/500
Door Closing Force
20
20
External ID
627779ac-0a7b-41b5-af55-1a4e62a32c73
627779ac-0a7b-41b5-af55-1a4e62a32c73
Location
Peabody Plaza
701 Market St, Ste 1230, St. Louis, MO
Phone: (314) 241-1175
701 Market St, Ste 1230, St. Louis, MO
Phone: (314) 241-1175
Owner
Attn: Daniel Hutkins
SPV XVII, LLC
701 Market St, Ste 1200, St. Louis, MO 63101
Phone: (314) 241-1175
Email: Daniel.hutkins@cbre.com
SPV XVII, LLC
701 Market St, Ste 1200, St. Louis, MO 63101
Phone: (314) 241-1175
Email: Daniel.hutkins@cbre.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (A) - Hoistways | (A)6 | No | No | 9th floor door closer arm needs to work. | 5/20/2020 |
| MO Minimum : Elevators | (A) - Hoistways | (A)3 | No | No | The hoistway door tension on P1, 2nd, 3rd, 4th, 10th, 11th, 12th, 13, and15th floor landings shall be adjusted to self-close. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of 8.6.The MCP shall include but not limited to examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The signage for “In Case of Fire” the missing. Install signage that conforms to the building code this elevator was installed to conform to. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | A number of guide rollers have degraded to the point of replacement is required on the elevator car and counterweight. Replace the degraded rollers. | |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: - In phase II operation, the car doors are required to open with constant pressure on the door open button. The car doors currently open automatically. Reinspection required. | 6/18/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | There is no signage for Firefighters Operation by the phase I and phase II key switches. Obtain the correct signage from the building code addition that this elevator was designed to conform to. | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Provide guards on car bulbs to prevent accidental contact or breakage. | |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Post Phase II operations in car. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Provide existing emergency lights to have two working bulbs. | |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Provide testing of the elevator on emergency power. | |
| A17.1-2016 : Elevators | 4.12 - Standby power selection switch | 8.6.4.19.7 (Re-Inspection) | Yes | No | Provide testing of the elevator emergency power selector switch. | |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | Yes | No | Provide testing of Phase I operations, record results. | |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | Yes | No | Provide testing of Phase II operations, record results. | |
| MO Minimum : Elevators | (A) - Hoistways | (A)3 | Yes | No | Numerous hoistway doors are not self closing, make so. Observed two broken door closer springs. | |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | Yes | No | Provide MCP |