Inspection
Inspection Details
Equipment ID
10025
10025
Inspection Date
6/18/2024
6/18/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Curtis Belew
Curtis Belew
Mechanic Name
Brenton Lane
Brenton Lane
Relief Valve Pressure
520
520
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
24F/25R
24F/25R
External ID
a52cab1d-bed1-4a92-99ef-95a3a2e2e815
a52cab1d-bed1-4a92-99ef-95a3a2e2e815
Location
Robinson Elementary School
803 Couch Ave, Kirkwood, MO
Phone: (314) 630-9847
803 Couch Ave, Kirkwood, MO
Phone: (314) 630-9847
Owner
Attn: Jimmy Hendrickson
Kirkwood R-7 School District
200 Thomas Ave, Kirkwood, MO 63122
Phone: (314) 213-6100 Ext: 8505
Email: invoices@kirkwoodschools.org
Kirkwood R-7 School District
200 Thomas Ave, Kirkwood, MO 63122
Phone: (314) 213-6100 Ext: 8505
Email: invoices@kirkwoodschools.org
Billing
Attn: Jimmy Hendrickson
Kirkwood R-7 School District
200 Thomas Ave, Kirkwood, MO 63122
Phone: (314) 213-6100 Ext: 8505
Email: jimmy.hendrickson@kirkwoodschools.org
Kirkwood R-7 School District
200 Thomas Ave, Kirkwood, MO 63122
Phone: (314) 213-6100 Ext: 8505
Email: jimmy.hendrickson@kirkwoodschools.org
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | 4"x 4" electrical junction box in machine room is missing its cover. Said junction box shall have a cover installed. | 9/4/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | In cab emergency telephone shall work. | 9/21/2018 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 7/22/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 1/4/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 8/26/2022 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | NEC - The sump pump shall have a maximum cord length of 6 feet. | 4/24/2026 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) | Yes | No | Verify the discharge capacity of the sump pump. | 7/13/2023 |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 2.1 | No | No | Seal the joint between the hoistway block walls and the building brick walls. | 4/24/2026 |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 2.1 | No | No | Seal all penetrations in the hoistway and machine room. | 4/24/2026 |
| A17.1-2016 : Elevators | 2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches | 2.29.1 | No | No | Install the elevator number on the main floor door jamb. | 4/24/2026 |
| A17.1-2016 : Elevators | 1.15 - sign and operating device symbols | 2.26.12 | No | No | Install a star on the main floor door jamb. | 4/24/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | An acceptance test tag is required. | 4/24/2026 |
| A17.1-2016 : Elevators | 2.14 - Code data plate | 8.6.1.5 | No | No | A code data plate is required. | 4/24/2026 |
| A17.1-2016 : Elevators | 1.9 - Power closing of doors or gates | 2.13.4.2.2 | No | No | Complete the door time labels. | 4/24/2026 |
| A17.1-2016 : Elevators | 1.7 - Car door or gate | 3.11 | No | No | Adjust the gap on the front cab door to not exceed 3/8". | 4/24/2026 |
| A17.1-2016 : Elevators | 2.6 - Ventilation | 2.7.9.2 | No | No | Install an A/C system in the machine room. | 4/24/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 1/19/2024 |
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.3.1 | No | No | A permanent and unobstructed means of access to the elevator machine room shall be provided. Note: During the test, the machine room door was partially blocked. This door shall not be blocked. | 4/24/2026 |
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | No | No | The machine room shall have a self-closing and self-locking door and shall be operable from the interior space without the use of a key. | 4/24/2026 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car telephone shall be operational. Note: The phone was tested 5 times. Each time it dialed out but wasn't answered. | 10/17/2024 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 4/24/2026 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | 4/24/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 3.26.10 | Yes | No | The auxiliary power lowering operation shall be functional. | 10/17/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall work. | 4/24/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a non-combustible frame with a clear protective vision plate over it. | 4/24/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Yes | No | Auxiliary power lowering operation is not functionsl and shall be repaired. | 7/24/2026 |