                        ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators
                     | 
                    
                        1.3 - Operating control devices
                     | 
                    
                        8.11.2.1.1(c)
                     | 
                    
                     | 
                    
                     | 
                    
                        The 1st floor call button failed to illuminate on the car operating panel as required. Repair or replace button to operate as required.
                     | 
                    
                        6/24/2025
                     | 
                
                
                    | 
                        ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators
                     | 
                    
                        5.1 - Pit access, lighting, stop switch, and condition
                     | 
                    
                        2.2.2 Design and Construction of Pits
                     | 
                    
                     | 
                    
                     | 
                    
                        The elevator pit shall be cleaned of dust and debris.
                     | 
                    
                        6/24/2025
                     | 
                
                
                    | 
                        MO Minimum : Elevators
                     | 
                    
                        (G) - Maintenance, Repair and Replacements
                     | 
                    
                        8.6.1.2.1 General Maintenance Requirements Documentation
                     | 
                    
                     | 
                    
                     | 
                    
                        A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of 8.6.The MCP shall include but not limited to examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals.
                     | 
                    
                        6/24/2025
                     | 
                
                
                    | 
                        MO Minimum : Elevators
                     | 
                    
                        (G) - Maintenance, Repair and Replacements
                     | 
                    
                        8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests)
                     | 
                    
                     | 
                    
                     | 
                    
                        Unusual testing procedures not outlined in A17.2 shall be present and accessible according to this code section. These include but not limited to procedures for tests, periodic inspections, maintenance, replacements, adjustments, and repairs for traction-loss detection means, broken-suspension-member detection means, residual-strength detection means, and related circuits.
                     | 
                    
                        6/24/2025
                     | 
                
                
                    | 
                        MO Minimum : Elevators
                     | 
                    
                        (G) - Maintenance, Repair and Replacements
                     | 
                    
                        8.6.1.4 Maintenance records
                     | 
                    
                     | 
                    
                     | 
                    
                        There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program.
                     | 
                    
                        6/24/2025
                     | 
                
                
                    | 
                        A17.1-2016 : Elevators
                     | 
                    
                        1.17 - Standby power operation
                     | 
                    
                        8.6.5.14.3(f)
                     | 
                    
                            x
                     | 
                    
                     | 
                    
                        Generator testing has not yet been tested and shall be tested to complete the inspection
                     | 
                    
                        7/6/2022
                     | 
                
                
                    | 
                        MO Minimum : Elevators
                     | 
                    
                        (G) - Maintenance, Repair and Replacements
                     | 
                    
                        8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
                     | 
                    
                     | 
                    
                     | 
                    
                        A written copy of the MCP shall be kept in the machine room for each unit
                     | 
                    
                        6/24/2025
                     | 
                
                
                    | 
                        ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators
                     | 
                    
                        2.13 - Governor,overspeed switch and seal
                     | 
                    
                        2.18
                     | 
                    
                            x
                     | 
                    
                     | 
                    
                        Governor remote trip function does not work, needs repaired. Re-inspection required
                     | 
                    
                        7/12/2025
                     | 
                
                
                    | 
                        ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators
                     | 
                    
                        3.8 - Top emergency exit
                     | 
                    
                        2.14.1.5
                     | 
                    
                     | 
                    
                     | 
                    
                        The elevator cab suspended ceiling emergency exit panel is not removable without the use of special tools, needs repaired
                     | 
                    
                        
                     | 
                
                
                    | 
                        MO Minimum : Elevators
                     | 
                    
                        (G) - Maintenance, Repair and Replacements
                     | 
                    
                        8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
                     | 
                    
                     | 
                    
                     | 
                    
                        A copy of the MCP shall be kept in the machine room for each unit
                     | 
                    
                        
                     | 
                
                
                    | 
                        ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators
                     | 
                    
                        2.13 - Governor,overspeed switch and seal
                     | 
                    
                        2.18
                     | 
                    
                            x
                     | 
                    
                     | 
                    
                        Governor remote trip function does not work, needs repaired. Re-inspection required
                     | 
                    
                        
                     |