Inspection
Inspection Details
Equipment ID
24476
24476
Inspection Date
6/21/2024
6/21/2024
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
na
na
Slide
39
39
Governor Rope Pull
350 / 1100
350 / 1100
Door Closing Force
24
24
External ID
e16054c1-dbce-4986-a7a4-1af02933cc32
e16054c1-dbce-4986-a7a4-1af02933cc32
Location
SSM SLUH Hospital
1201 S Grand Blvd, St. Louis, MO
Phone: (314) 257-1152
Email: patrick.schubert@ssmhealth.com
1201 S Grand Blvd, St. Louis, MO
Phone: (314) 257-1152
Email: patrick.schubert@ssmhealth.com
Owner
Attn: Brandy Kary
SSM Health- ESEP Department
1015 Corporate Square, Ste 160, St. Louis, MO 63132
Phone: (314) 257-1152
Email: brandy.kary@ssmhealth.com
SSM Health- ESEP Department
1015 Corporate Square, Ste 160, St. Louis, MO 63132
Phone: (314) 257-1152
Email: brandy.kary@ssmhealth.com
Billing
Attn: Patrick Schubert, Director, Plant Operations
SSM SLU Hospital
1201 S Grand Blvd, St. Louis, MO 63110
Phone: (314) 257-1152
Email: Patrick.schubert@ssmhealth.com
SSM SLU Hospital
1201 S Grand Blvd, St. Louis, MO 63110
Phone: (314) 257-1152
Email: Patrick.schubert@ssmhealth.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | The elevator pit shall be cleaned of dust and debris. | 6/24/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of 8.6.The MCP shall include but not limited to examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals. | 6/24/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) | No | No | Unusual testing procedures not outlined in A17.2 shall be present and accessible according to this code section. These include but not limited to procedures for tests, periodic inspections, maintenance, replacements, adjustments, and repairs for traction-loss detection means, broken-suspension-member detection means, residual-strength detection means, and related circuits. | 6/24/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. | 6/24/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.5.14.3(f) | Yes | No | Generator testing has not yet been tested and shall be tested to complete the inspection | 7/6/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | The elevator pit shall be cleaned of dust and debris. | 6/24/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Perform 125% brake test and unintended movement test. Re-inspection required | 5/15/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A written copy of the MCP shall be kept in the machine room for each unit | 6/24/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) | No | No | Unique procedures or methods for tests and inspections not described in A17.2 shall be kept in the elevator machine room | 6/24/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Need to test elevator on phase I & II. Re-inspection required | 7/9/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Need to clean trash from the pit | 6/24/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test incomplete, need to perform the following tests to complete inspection: Test elevator for operation on emergency power, perform unintended car movement test with no load in car, perform 125% brake test and unintended movement test with 125% of rated load. Re-inspection required | 7/9/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) | No | No | Unique procedures or methods for tests and inspections not described in A17.2 shall be kept in the elevator machine room | 6/24/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) | No | No | Unique procedures or methods for tests and inspections not described in A17.2 shall be kept in the elevator machine room | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Need to clean trash from elevator pit | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test incomplete, need to perform the following tests to complete inspection: Perform unintended car movement test with no load in the up direction, perform 125% brake test and unintended movement test with 125% of rated load. Re-inspection required |