Inspection
Inspection Details
Equipment ID
16257
16257
Inspection Date
7/2/2024
7/2/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Dennis Smith
Dennis Smith
Mechanic Name
Relief Valve Pressure
N/A
N/A
Slide
6"
6"
Governor Rope Pull
N/A
N/A
Door Closing Force
20
20
External ID
fac692b8-609e-4393-8e80-06e7787e3c0c
fac692b8-609e-4393-8e80-06e7787e3c0c
Location
Lofts at 415
415 N 3rd St, St. Joseph, MO
Phone: (816) 749-4663
415 N 3rd St, St. Joseph, MO
Phone: (816) 749-4663
Owner
Attn: CAA 3 LLC
CAA 3 LLC
3432 E Russell St, Nesa, AZ 85213
Phone: (000) 000-0000
CAA 3 LLC
3432 E Russell St, Nesa, AZ 85213
Phone: (000) 000-0000
Billing
Attn: Ashley Casella
Mitchell Park Plaza
1300 S 11th St, Ste 100, St. Joseph, MO 64503
Phone: (816) 749-4663
Email: ashley@epic-pm.com
Mitchell Park Plaza
1300 S 11th St, Ste 100, St. Joseph, MO 64503
Phone: (816) 749-4663
Email: ashley@epic-pm.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | Provide tye ABC fire extinguisher inside control room near access door | 7/29/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate | 7/26/2019 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Test and log firefighter operation monthly | 8/24/2021 |
| A17.1-1996 : Elevators | 1.15 - sign and operating device symbols | 1001.2(a)(15) | No | No | Replace broken bezel identification marking for firefighter keyswitch | 8/24/2021 |
| A17.1-1996 : Elevators | 3.26 - Broken rope, chain, or tape switch | 1001.2(c)(9) | Yes | No | Slack belt switch does not function. | 8/13/2021 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Test and log firefighter operation monthly | 8/24/2021 |
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 204 | No | No | Replace missing car direction lantern fixture in car enclosure opening. | 9/12/2024 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | No MCP | 9/12/2024 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(a)(1) | No | No | No maintenance records on site | 9/12/2024 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2(b)(5) | No | No | Written procedures for tests and inspections need to be kept in the control room. | 9/12/2024 |
| A17.1-2016 : Elevators | 2.29 - Car and counterweight safeties | 8.6.4.19.2 | Yes | Yes | Perform annual no load safety test | 8/21/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Post In Case of Fire signage next to hall button fixture at each landing | 9/12/2024 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed | 9/12/2024 |
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 204 | No | No | Replace missing car direction lantern fixture in the car enclosure | 9/12/2024 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | Pit access door needs to be self-locking | 9/12/2024 |
| A17.1-1996 : Elevators | 2.8 - Pipes, wiring, and ducts | 102.2 | No | No | Install heat detector within 24 inches from each machine room sprinkler | 9/12/2024 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate | 8/22/2023 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | No | No | Post firefighter instructions next to hall firefighter keyswitch | 9/12/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Post In Case of Fire signage next to hall button fixture at each landing | 9/12/2024 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | No maintenance control plan on site | 9/12/2024 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(a)(1) | No | No | No maintenance records on site | 9/12/2024 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2(b)(5) | No | No | Keep written procedures for tests and inspections on site | 9/12/2024 |
| A17.1-2016 : Elevators | 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection | 8.6.4.20.11 (Re-Inspection) | Yes | No | Perform unintended motion and ascending car protection tests | 8/22/2023 |
| A17.1-2016 : Elevators | 2.29 - Car and counterweight safeties | 8.6.4.20.1 | Yes | No | Perform full load safety test | 8/22/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed in the control space. | 9/12/2024 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate | 7/2/2024 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | No | No | DOOR CLOSE BUTTON IS LABELED #1 | 9/12/2024 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.1a | No | No | HOLE IN MACHINE ROOM CELING NEEDS TO BE PATCHED AND FIRE RATED | 9/12/2024 |
| A17.1-1996 : Elevators | 1.7 - Car door or gate | 204.4 | No | No | CAR DOOR GAP IS >1/2" . NEEDS TO BE ADJUSTED | 9/12/2024 |
| A17.1-1996 : Elevators | 1.7 - Car door or gate | 204.6 | No | No | DOOR GAP IS >1/2'' | 6/27/2025 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | SUPPLY WORKING LIGHT AND BELL | 4/29/2026 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | PROVIDE WORKING PHONE |