Inspection
Inspection Details
Equipment ID
2327
2327
Inspection Date
6/26/2024
6/26/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Dennis Smith
Dennis Smith
Mechanic Name
Dennis Smith
Dennis Smith
Relief Valve Pressure
350
350
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
15
15
External ID
51bbf5f3-ac61-4892-9f6c-da59e9c03398
51bbf5f3-ac61-4892-9f6c-da59e9c03398
Location
Housing Unit #10
3401 Faraon St, St. Joseph, MO
Phone: (816) 387-2158
Email: linda.weis@doc.mo.gov
3401 Faraon St, St. Joseph, MO
Phone: (816) 387-2158
Email: linda.weis@doc.mo.gov
Owner
Attn: INTERAGENCY
WRDCC-INTERAGENCY
3401 Faraon St, St. Joseph, MO 64506
Phone: (000) 000-0000
Email: CHRIS.POLACHEK@DOC.MO.GOV
WRDCC-INTERAGENCY
3401 Faraon St, St. Joseph, MO 64506
Phone: (000) 000-0000
Email: CHRIS.POLACHEK@DOC.MO.GOV
Billing
Attn: INTERAGENCY
WRDCC-INTERAGENCY
3401 Faraon St, St. Joseph, MO 64506
Phone: (000) 000-0000
WRDCC-INTERAGENCY
3401 Faraon St, St. Joseph, MO 64506
Phone: (000) 000-0000
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | Emergency bell does not operate | 7/22/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Need to remove water and oil from pit. Pits need to be kept dry. | 4/8/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light does not operate. | 4/8/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency bell does not operate. | 11/8/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Test and log firefighter operation monthly | 9/8/2021 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Exposed door motor leads need to be in metal conduit | 9/8/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Cylinder drain line needs to drain into pit collection container. | 9/8/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove water and oil mixture from pit. Pit needs to be kept clean and dry. | 9/8/2021 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Firefighter phase 2 operation does not override security. 14 days to repair or red tagged. May apply for variance from the state. | 9/8/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | Yes | Yes | Replace plunger seal. Plunger seal blew out during pressure relief testing. | 4/12/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | No MCP | 4/12/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | MRL not up to date | 4/12/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed. | 4/12/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | COVER HOLE IN PIT FLOOR | 8/8/2024 |