Inspection
Inspection Details
Equipment ID
2846
2846
Inspection Date
11/16/2018
11/16/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Dixon Liljegren
Dixon Liljegren
Mechanic Name
Michael Bales
Michael Bales
Relief Valve Pressure
Slide
Governor Rope Pull
0
0
Door Closing Force
28
28
External ID
a4adfb26-2916-41d1-8432-251ba2db5a92
a4adfb26-2916-41d1-8432-251ba2db5a92
Location
Hotel Bothwell
103 E 4TH ST, SEDALIA, MO
103 E 4TH ST, SEDALIA, MO
Owner
Furnell Investments
501 S OHIO AVE, SEDALIA, MO 65301-4406
501 S OHIO AVE, SEDALIA, MO 65301-4406
Billing
Attn: Hotel Bothwell
103 E 4TH ST, SEDALIA, MO 65301-4401
103 E 4TH ST, SEDALIA, MO 65301-4401
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency phone not working. Alarm bell ok. | 11/17/2022 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.2-211.8 | Yes | Yes | Mod in 2004, Phase I 2.27.3.1.6(a) violation recalled to alternate floor. Phase 11. 2.27.3.3.1 Phase ii operation not functional Red Tagged Car. | 2/24/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | No | Machine room door must be self-closing and self-locking. | 3/31/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | No | Wall separating machine room is combustible material. Not fire rated | 3/31/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | Yes | No | Large plumbing pipe in access path. Variance is requested. | 3/31/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)5 | Yes | No | Ladder needed in pit | 3/31/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | Yes | No | Light needed in pit | 3/31/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)7 | Yes | No | Additional stop switch needed in deep pit | 3/31/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | Yes | No | A wooden partial platform between pit floor and buffers attached to the front of hoistway wall is not needed for elevator operation. | 3/31/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door must be self-closing and self-locking | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Needs non combustible separation of machine room | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Existing pipe prevents unobstructed path to machine room | |
| MO Minimum : Elevators | (I) - Pits | (I)5 | No | No | Ladder needed in pit | |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Light needed in pit | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Wooden platform in pit not needed for elevator operation | |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Needs pit light | |
| MO Minimum : Elevators | (I) - Pits | (I)5 | No | No | Needs pit ladder | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Wooden platform in pit | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Need unobstructed path to machine room. Existing large plumbing pipe may need variance. | |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light mounted but not wired yet Need to complete | |
| MO Minimum : Elevators | (I) - Pits | (I)5 | No | No | Pit access ladder needed to be installed |