Inspection
Inspection Details
Equipment ID
7991
7991
Inspection Date
7/3/2024
7/3/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
21
21
External ID
3c0e2bf3-1163-4578-a21c-5b237f21aefc
3c0e2bf3-1163-4578-a21c-5b237f21aefc
Location
MO Baptist Medical Center- Bldg D
3023 N Ballas Rd, St. Louis, MO
Phone: (314) 922-9339
3023 N Ballas Rd, St. Louis, MO
Phone: (314) 922-9339
Owner
Attn: BJC C/O Cushman Wakefield
BJC C/O Cushman Wakefield
8300 Eager Rd, St. Louis, MO 63144
Phone: (000) 000-0000
Email: bjcinvoices@cushwake.com
BJC C/O Cushman Wakefield
8300 Eager Rd, St. Louis, MO 63144
Phone: (000) 000-0000
Email: bjcinvoices@cushwake.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Complete annual insption-test fire service | 5/28/2019 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Car would not operate on emergency power. Emergency operation of the elevator shall function and be tested. | 10/14/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean the pit of dirt and debris. | 12/28/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) | No | No | Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. | 12/28/2022 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Ropes are undersized and have excessive rouging. | 3/1/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Emergency power operation of the elevator shall be tested. All units in Building D are due for this testing. | 3/1/2024 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Ropes are undersized and have excessive rouging. (Violation still not corrected/re-inspected as on 3/1/24) | 7/3/2024 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Ropes are undersized and have excessive rouging. This violation has been cited 2 times prior and has not been fixed. Third and final reinspection within 15 days (7/18/24), if not compliant, unit must be red-tagged and removed from service. | 7/31/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall work. Dials, answered, operator can hear us, but we cannot understand her (intermittent speaker). | 7/31/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 11/14/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit shall be kept clean. Remove excess debris. | 11/14/2025 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)1(A) | No | No | The suspension ropes shall be tagged as specified by CSR 40-5.065(L)1. A tag was not provided for the new ropes. | 11/14/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pits shall not be used for storage purposes. There are two large extension ladders being stored in the pit. | 11/14/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall work. Dials, answered, operator can hear us, but we cannot understand her (intermittent speaker). Violation not cleared as of 7/31/2024. | 11/14/2025 |