Inspection
Inspection Details
Equipment ID
3790
3790
Inspection Date
11/20/2018
11/20/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Harris
David Harris
Mechanic Name
Relief Valve Pressure
410
410
Slide
Governor Rope Pull
Door Closing Force
22
22
External ID
0a1e7ae0-6a69-4f47-b685-f61b579df0e0
0a1e7ae0-6a69-4f47-b685-f61b579df0e0
Location
Sunset Village
14275 HIGHWAY Z, SAINT ROBERT, MO
14275 HIGHWAY Z, SAINT ROBERT, MO
Owner
Luther Thomas & Jim Dobbs
14275 HIGHWAY Z, SAINT ROBERT, MO 65584-3255
14275 HIGHWAY Z, SAINT ROBERT, MO 65584-3255
Billing
Attn: Luther Thomas & Jim Dobbs
14275 HIGHWAY Z, SAINT ROBERT, MO 65584-3255
14275 HIGHWAY Z, SAINT ROBERT, MO 65584-3255
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | The fire extinguisher is expired. An up to date inspection tag shall be installed on the fire extinguisher. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 10/16/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | 10/16/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.36 - Hydraulic Cylinders | 8.11.3.1.2(s) | Yes | No | This elevator is equipped with a life jacket. A category 5 test is due on the life jacket. | 5/4/2023 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Must post current state operating Cert. in Machine room. 5.100(2) | |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Must provide current test tag on Machine room Fire Extinguisher. 8.6.1.6.5 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.5.2 Collection of Oil Leakage | No | No | Must provide means to monitor oil loss. ( currently jack overflow tubes routed back to tank.) 8.6.5.5.2 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2 On-Site Documentation | No | No | Must provide and maintain on site MCP (maintenance control program). 2.40 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Must provide current test tag on machroom fire extinguisher. | |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Must post current state operating Cert. in Mach room. 5.100(2) | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.5.2 Collection of Oil Leakage | No | No | Must provide means to monitor oil loss from jack packing gland. 8.6.5.5.2 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2 On-Site Documentation | No | No | Must provide and maintain all required MCP doc. on site. 8.6.1.2.2 |