Inspection
Inspection Details
Equipment ID
21774
21774
Inspection Date
11/19/2018
11/19/2018
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
Robert Kehm
Robert Kehm
Relief Valve Pressure
Slide
12
12
Governor Rope Pull
65/285
65/285
Door Closing Force
29
29
External ID
d698bfa4-4b9e-4991-be8a-59e040f9ad19
d698bfa4-4b9e-4991-be8a-59e040f9ad19
Location
River City Casino Hotel
777 RIVER CITY CASINO BLVD, SAINT LOUIS, MO
777 RIVER CITY CASINO BLVD, SAINT LOUIS, MO
Owner
Attn: River City Hotel
PNK (River City) LLC
777 RIVER CITY CASINO BLVD, SAINT LOUIS, MO 63125-1019
PNK (River City) LLC
777 RIVER CITY CASINO BLVD, SAINT LOUIS, MO 63125-1019
Billing
Attn: PNK (River City) LLC
River City Hotel
777 RIVER CITY CASINO BLVD, SAINT LOUIS, MO 63125-1019
River City Hotel
777 RIVER CITY CASINO BLVD, SAINT LOUIS, MO 63125-1019
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone in elevator cab does not work, line problem. Re-inspection required | 4/10/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not operating correctly. Check and repair the programming of this phone for proper operation and passenger safety. Reinspection required in 14 days. | 4/3/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | No | No | Multiple pickup rollers are damaged on hoistway doors. The pickup rollers shall be replaced and the car door clutch adjusted to activate without damaging rollers. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The handrail in the elevator car has been removed and shall be reinstalled to comply with ADA requirements. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | The handrail in the elevator car has been removed and shall be re-installed to comply with ADA requirements | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevator appears to have emergency generator backup power operation, which needs to be tested to complete inspection. Re-inspection required | 5/21/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | The handrail in the elevator has been removed and shall be re-installed to comply with ADA requirements | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | The handrail in the elevator cab has been removed, needs to be re-installed to comply with ADA requirements | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | The handrail in the elevator car has been removed and needs to be re-installed to comply with ADA requirements | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Emergency power needs to be tested. Re-inspection required | 4/9/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | The handrail in the elevator car has been removed and shall be re-installed to comply with ADA requirements | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | The handrail in the elevator car has been removed and shall be reinstalled to comply with ADA requirements |