Inspection
Inspection Details
Equipment ID
22449
22449
Inspection Date
10/18/2017
10/18/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Unknown Conversion
Unknown Conversion
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
Location
IKEA Property
#1 IKEA Way, St. Louis, MO
Phone: (314) 721-0410
#1 IKEA Way, St. Louis, MO
Phone: (314) 721-0410
Owner
IKEA Property
# 1 IKEA Way, St. Louis, MO 63110
# 1 IKEA Way, St. Louis, MO 63110
Billing
Attn: IKEA Property
# 1 IKEA Way, , MO 63110
# 1 IKEA Way, , MO 63110
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.17 - Step/skirt clearances, panels, and performance index | 6.1.3.3.5 | No | No | Step indexing could not be completed due to out of calibration equipment. Reinspection Required. | 11/26/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 8.1 - Machinery space access, lighting, receptacle, and condition | 8.6.8.13 | No | No | Clean escalator pit. | 1/23/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.5 - Lighting | 8.6.11.5(i) Demarcation Lighting (Re-Inspect) | Yes | No | Upper demarcation lights not working | 12/17/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.17 - Step/skirt clearances, panels, and performance index | 6.1.3.3.9 Step/Skirt Performance Index | Yes | No | Unit failed indexing,repair as needed. | 12/17/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.19 - Maintenance records | 8.6.1.4 | No | No | Provide MCP | 1/23/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.7 - Combplate and comb step impact device | 6.1.6.3.13 | Yes | No | Comb plate impact switches could not be tested due to comb plate screws being stripped out, repair and perform comb plate impact switch tests. Re-inspection required | 5/23/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 8.1 - Machinery space access, lighting, receptacle, and condition | 8.6.8.13 | No | No | Need to clean dirt & debris from escalator pits | 1/23/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 8.1 - Machinery space access, lighting, receptacle, and condition | 8.6.1.6.3 | No | No | Provide electrical prints for escalator | 1/23/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.5 - Lighting | 8.6.11.5(i) Demarcation Lighting (Re-Inspect) | Yes | No | Repair step demarcation lights at both landings. Re-inspection required | 8/14/2025 |
| A17.1-2016 : Elevators | 7.5 - Lighting | 6.1.7.2 | No | No | Demarcation Light not working at top or bottom. | 1/23/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 8.1 - Machinery space access, lighting, receptacle, and condition | 8.11.4.2.1 (Re-Inspection) | Yes | No | Escalator truss shall get a clean down |