Inspection
Inspection Details
Equipment ID
13469
13469
Inspection Date
7/18/2024
7/18/2024
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Thomas McGrath
Thomas McGrath
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
250/600 CW 35/850
250/600 CW 35/850
Door Closing Force
NA
NA
External ID
d4402aac-9ee8-4dcc-b66f-d9b4fc9487d3
d4402aac-9ee8-4dcc-b66f-d9b4fc9487d3
Location
Hanley Cooperation Tower
101 S Hanley Rd, Clayton, MO
Phone: (314) 655-5874
101 S Hanley Rd, Clayton, MO
Phone: (314) 655-5874
Owner
Attn: James Scott | Property Manager
Hanley Corporate Tower
101 S Hanley Rd, Ste 400, Clayton, MO 63105
Phone: (314) 269-1863
Email: JScott@lpc.com
Hanley Corporate Tower
101 S Hanley Rd, Ste 400, Clayton, MO 63105
Phone: (314) 269-1863
Email: JScott@lpc.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)1(A) | No | No | Rope grippers need repair | 10/16/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Need maintenance control program on site posted on controller | 2/12/2021 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Rope came out of the groove on the sheave at the top of the hoistway | 2/11/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Need to include testing procedures in MCP on or before January 1,2022 | 9/17/2021 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service and document on log in machine room | 10/23/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) | No | No | Provide testing procedures in the maintenance control program | 10/23/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean pit, | 10/23/2024 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Replace hoist ropes red rouge reduced diameter | 7/21/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Repair replace deflector sheave within 60 days | 10/23/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Complete annual test within 14 days unintended motion alternate fire floor | 7/21/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Repair emergency light and bell | 7/21/2022 |
| A17.1-2016 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11.1.4(b)(1) Electric elevator, dumbwaiter, or material lift Placed out of Service | Yes | Yes | Complete 5 year testing..reinspection required within 14 days | 9/16/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Repair emergency light in car | 9/16/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Test emergency generator | 9/16/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | Yes | No | Complete 5 yr test (Fire Service) Reinspection required | 2/8/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Test Emergency generator reinspection required within 30 days | 2/8/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test is incomplete, need to perform the following tests to complete inspection: Fire service, Emergency standby power & unintended motion were not tested. Re-inspection required | 4/7/2026 |