Inspection
Inspection Details
Equipment ID
14134
14134
Inspection Date
6/14/2024
6/14/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Brian Foster Sr.
Brian Foster Sr.
Relief Valve Pressure
380
380
Slide
n/a
n/a
Governor Rope Pull
n/a
n/a
Door Closing Force
21
21
External ID
9398ecf5-3f62-448a-8117-e3f2d1de5061
9398ecf5-3f62-448a-8117-e3f2d1de5061
Location
Historic Ballantine House
409 High St, Booneville, MO
Phone: (800) 635-0212
409 High St, Booneville, MO
Phone: (800) 635-0212
Owner
Attn: Phone = Matt / Alt phone = Daniel
Frontier Property Management
417 Main St, Ste B, Boonville, MO 65233
Phone: (660) 537-2213
Alt Phone: (660) 888-8436
Email: matt@314rent.com
Frontier Property Management
417 Main St, Ste B, Boonville, MO 65233
Phone: (660) 537-2213
Alt Phone: (660) 888-8436
Email: matt@314rent.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light battery is dead and needs to be replaced | 7/27/2022 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | emergency phone line is dead, provide a working phone line to the elevator controller | 7/27/2022 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(c)(2) | No | No | monthly fire service test log is to be kept in the machine room | 6/14/2024 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2 On-Site Documentation | No | No | provide maintenance control program on site documents | 6/14/2024 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.11.3.1.2(j) | No | No | Machine room fire extinguisher last checked in 2019 | 6/14/2024 |
| A17.1-2016 : Elevators | 1.4 - Sills and car floor | 8.11.3.1.1(d) | No | No | repair the grout in the bottom landing sill, it is crumbling and a trip hazard | 6/14/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | inspection tag on the fire extinguisher in the machine room is from 2019, have the fire extinguisher inspected and tagged annually | 6/14/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | the copy of the state operating certificate in the machine room is from 2017, post a new copy of the state certificeate in the machine room annually when received from the state | 6/14/2024 |
| A17.1-1996 : Elevators | 1.4 - Sills and car floor | 110.11a | No | No | the bottom landing hoistway door sill has not been grouted, there is a gap between the concrete floor and the hoistway door sill | 6/14/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | the phone line for the emergency phone did not work, provide a working phone line | 7/26/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | No | No | perform a monthly fire service test and fill out the log in the machine room | 6/14/2024 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1(a)(3) Battery Backup Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | the backup battery for the emergency phone is not working, phone will not call out when the 110 volt power is off | 10/16/2023 |
| A17.1-1996 : Elevators | 3.3 - Top-of-car operating device | 210.1d | No | No | the top of car operating device, would not run in the down direction on car top inspection | 7/26/2023 |