Inspection
Inspection Details
Equipment ID
2124
2124
Inspection Date
7/18/2024
7/18/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Dennis Smith
Dennis Smith
Mechanic Name
Jerry Reasoner
Jerry Reasoner
Relief Valve Pressure
410
410
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
>35
>35
External ID
bd9cd804-69a3-42fc-a36f-2c4efcdcf359
bd9cd804-69a3-42fc-a36f-2c4efcdcf359
Location
Conception Abbey
37174 State Hwy VV, Conception, MO
Phone: (660) 944-3100
37174 State Hwy VV, Conception, MO
Phone: (660) 944-3100
Owner
Attn: Mark Wiederholt
Conception Abbey
37174 State Hwy VV, Conception, MO 64433
Phone: (660) 944-2968
Email: markw@conception.edu
Conception Abbey
37174 State Hwy VV, Conception, MO 64433
Phone: (660) 944-2968
Email: markw@conception.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light does not illuminate. | 7/31/2018 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Cylinder drain lines need to removed from tank. Cylinder drain lines need to drain into seperate pit containers that are covered and no more than 5 gallon capacity. | 3/23/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light does not illuminate. Need to provide pit lighting. | 3/23/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | No | No | Test and log firefighter operation monthly | 9/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Cylinder drain lines run back to storage tank. Remove from storage tank and install in pit collection containers | 9/16/2025 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Install covers on 4x4 junction boxes located on hoistway wall. | 9/16/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light does not illuminate. No electrical power at light fixture. Need to provide power to pit light fixture. | 9/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Cylinder drain lines shall be ran to pit collection container and not the hydraulic storage tank in the machine roo.. | 9/16/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light does not illuminate. No power at light fixture. Circuit breaker or wiring issue. | 9/16/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)12 (Door open zones) | Yes | No | ADJUST DOOR RESTRICTOR SO IT WORKS | 7/8/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | REPLACE SUMP PUMP COVER ( IT IS IN THE PIT) | 9/16/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | REMOVE STANDING OIL FROM PIT | 9/16/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)7 | No | No | REDUCE THE CLOSING FORCE TO <30 LBS | 9/16/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | CLEAN OIL FROM PIT FLOOR AND REPAIR LEAK | 9/16/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | INSTALL SUMP COVER | 9/16/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | INSTALL A SELF CLOSER ON MACHINE ROOM DOOR |