Inspection
Inspection Details
Equipment ID
20220
20220
Inspection Date
7/3/2024
7/3/2024
Inspection Type
Reinspection
Reinspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
James DeBell
James DeBell
Relief Valve Pressure
Na
Na
Slide
Na
Na
Governor Rope Pull
25 / 750
25 / 750
Door Closing Force
Na
Na
External ID
d65d4026-898c-4793-98a1-076d87ba923a
d65d4026-898c-4793-98a1-076d87ba923a
Location
River City Casino
777 River City Casino Blvd, St. Louis, MO
Phone: (314) 388-7777
777 River City Casino Blvd, St. Louis, MO
Phone: (314) 388-7777
Owner
Attn: River City Hotel
PNK (River City) LLC
777 River City Casino Blvd, St. Louis, MO 63125
Phone: (314) 681-9894
Email: Charles.sheard@pngaming.com
PNK (River City) LLC
777 River City Casino Blvd, St. Louis, MO 63125
Phone: (314) 681-9894
Email: Charles.sheard@pngaming.com
Billing
Attn: River City Hotel
PNK (River City) LLC
777 River City Casino Blvd, St. Louis, MO 63125
Phone: (314) 681-9894
Email: coupainvoicing@pngaming.com
PNK (River City) LLC
777 River City Casino Blvd, St. Louis, MO 63125
Phone: (314) 681-9894
Email: coupainvoicing@pngaming.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | No | No | Remove all unrelated storage from elevator equipment room. | 11/17/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 6/15/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone in elevator cab is not working, line problem. Re-inspection required | 4/11/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not operating correctly. Check and repair the programming of this phone for proper operation and passenger safety. Reinspection required in 14 days. | 5/21/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA phone inside the elevator is not operating correctly. Check and repair the programming of this phone for proper operation and passenger safety. Re-inspection required | 6/13/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The following tests need to be performed to complete inspection: full load, full speed safeties, unintended movement, fire service, safeties pull out, governor pull thru & 125% brake. Re-inspection required | 7/3/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not operating correctly. Check & repair the programming of this phone for proper operation and passenger safety. Re-inspection required | 7/3/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | Yes | Test failed, need to perform the following tests to complete Cat 5 full load test: Test car safeties with rated load at rated speed, test governor rope pull thru force, Perform unintended movement test. Test drive machine brake with 125% of rated load. Phase I & II fire service. Unit Red-tagged, Re-inspection required | 8/23/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not operating correctly. Re-inspection required | 8/23/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | Yes | The elevator ADA telephone inside the elevator is not operating correctly. Check and repair programming of the phone for proper operation and passenger safety. Note: This phone has not been operational since 6/2022. Elevator Red Tagged due to this issue. | 10/1/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Emergency power needs to be tested. Re-inspection required | 4/9/2025 |