Inspection
Inspection Details
Equipment ID
26029
26029
Inspection Date
7/10/2024
7/10/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Brenton Lane
Brenton Lane
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
15
15
External ID
ec8a980c-0023-4180-a62c-15685f56b8d0
ec8a980c-0023-4180-a62c-15685f56b8d0
Location
21c Museum Hotel
1528 Locust St, St. Louis, MO
Phone: (314) 781-8000
1528 Locust St, St. Louis, MO
Phone: (314) 781-8000
Owner
Attn: Locust Street Property 1 STL, LLC
Locust Street Property 1 STL, LLC
1528 Locust St, St. Louis, MO 63103
Phone: (314) 781-8000
Email: boverbaugh@russellco.com
Locust Street Property 1 STL, LLC
1528 Locust St, St. Louis, MO 63103
Phone: (314) 781-8000
Email: boverbaugh@russellco.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Acceptance testing is incomplete. The following items still need to be tested and recorded: Slide, pull out/pull thru, governor electrical & mechanical speeds, door closing pressure, ring & string, Phase 1 & 2 key switch testing, fire alarm initiating device testing, emergency power, emergency light and bell. | 5/3/2023 |
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | Yes | No | Machine room door shall be self-closing and self-locking and shall be operable from the interior space without the use of a key. Door does not have lock/handle installed. | 5/3/2023 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | 2-way commination device shall be operational. | 5/3/2023 |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 2.1 | Yes | No | Hoistway penetrations, holes, and seams shall be appropriately filled with fire proofing materials. | 5/3/2023 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.3 | Yes | No | The heat detector in the pit shall activate the shunt trip disconnect. Any heat detector in a shared pit shall shunt all elevators that share the same pit. | 5/4/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | Yes | Two stop switches in pit are not working. Elevator Red Tagged. | 7/19/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Due to other elevator failures at this location only emergency power and fire service testing were completed. The remainder of the category 1 test and annual inspection shall be completed. | 5/21/2025 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 2/18/2026 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall work. | 2/18/2026 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The phone is still not functional (2nd notice) | 4/23/2026 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone not working, noted from Annual on 2/9/2026 | 4/28/2026 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | ALARM BELL SHALL WORK WITH LOSS OF MAIN 120v POWER | |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Elevators that are equipped to operate on Emergency Power shall be tested operating on Em Power, Annually | |
| A17.1-2016 : Elevators | 2.17 - Drive machine brake | 2.24.8.3 | Yes | No | Emergency Brake Release system shall work. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | 5yr test tags shall be attached to Governor, releasing carrier, buffers, etc. | |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | Fire Service must be tested and properly documented monthly on Log Sheet | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Governor rope shall have proper data tag(s | |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Pit shall be kept clean. Remove excess debris. |