Inspection
Inspection Details
Equipment ID
18525
18525
Inspection Date
10/24/2018
10/24/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Ledden
Michael Ledden
Mechanic Name
Richard Toeniskoetter
Richard Toeniskoetter
Relief Valve Pressure
420
420
Slide
Governor Rope Pull
Door Closing Force
27
27
External ID
50ba6902-9b6e-4087-98a1-2501da032d91
50ba6902-9b6e-4087-98a1-2501da032d91
Location
Winghaven Country Club
7777 WINGHAVEN BLVD, O FALLON, MO
7777 WINGHAVEN BLVD, O FALLON, MO
Owner
McWing Golf, LLC
7777 WINGHAVEN BLVD, O FALLON, MO 63368-3788
7777 WINGHAVEN BLVD, O FALLON, MO 63368-3788
Billing
Attn: McWing Golf, LLC
7777 WINGHAVEN BLVD, O FALLON, MO 63368-3788
7777 WINGHAVEN BLVD, O FALLON, MO 63368-3788
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 3.3 - Top-of-car operating device | 1001.2(c)(3) | Top of car inspection station shall work. | 1/17/2019 | ||
| A17.1-1996 : Elevators | 1.1 - Door Re-opening device | 1001.2(a)(1) | Photo edge shall work correctly, currently only works intermittently. | 1/17/2019 | ||
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | Emergency light shall work. | 1/17/2019 | ||
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency alarm bell shall work. | 1/30/2019 | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | x | The emergency alarm and phone shall be operational when 110v source is removed. - Elevator Red Tagged. | 12/15/2021 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | x | The in car emergency lighting shall be operational when 110v source is removed. | 12/15/2021 | |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) | 12/14/2021 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | The emergency alarm bell shall be operational. | 11/8/2023 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | x | The emergency light shall be operational. | 11/8/2023 | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The emergency bell is not working. | 11/18/2024 | |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | x | The emergency light is not working. | 11/18/2024 | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | 2-way communication device shall work. Phone line dead (0V measured) | ||
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | Machine room shall have proper fire extinguisher and shall have current monthly/annual test tag. | |||
| A17.1-1996 : Elevators | 2.4 - Machine space | 1001.2(b)(4) | Non-elevator related items shall not be stored in the machine room. (pressure washer, misc materials) |