Inspection
Inspection Details
Equipment ID
26359
26359
Inspection Date
7/8/2024
7/8/2024
Inspection Type
New Installation
New Installation
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Richard Toeniskoetter
Richard Toeniskoetter
Relief Valve Pressure
495
495
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
20F/22R
20F/22R
External ID
3c76a998-5b13-4a4e-b81e-1a900ccfc259
3c76a998-5b13-4a4e-b81e-1a900ccfc259
Location
Francis Howell North High School
2549 Hackmann Rd, St. Charles, MO
Phone: (314) 717-8528
Email: matt.frank@smwilson.com
2549 Hackmann Rd, St. Charles, MO
Phone: (314) 717-8528
Email: matt.frank@smwilson.com
Owner
Attn: Matt Frank
Francis Howell School District
2549 Hackmann Rd, St. Charles, MO 63303
Phone: (314) 717-8528
Email: matt.frank@smwilson.com
Francis Howell School District
2549 Hackmann Rd, St. Charles, MO 63303
Phone: (314) 717-8528
Email: matt.frank@smwilson.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall work. | 7/20/2024 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1.1.6 Verification of Telephone Operability | Yes | No | Communication loss buzzer shall work. | 7/20/2024 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.7.9.1 | Yes | No | Machine space lighting shall be at least 19 foot-candles at floor. | 7/20/2024 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | Yes | No | Provide code compliant fire extinguisher at/near machine space. | 7/20/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | Yes | No | Main and lighting disconnects shall have feed locations labeled. | 7/20/2024 |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 2.1 | Yes | No | Repair hoistway fire penetrations/fire caulk. | 7/20/2024 |
| A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | Yes | No | Missing 4x4 electrical box cover is hoistway. | 7/20/2024 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 | Yes | No | Pit light and outlet not working (1 of 3 fixtures). | 7/20/2024 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2 Phase I Operation Recall by Initiating Device | Yes | Yes | FAID test failed. Hoistway smoke did not recall. Heat detector on ML to be relocated to within 2' of sprinkler. | 7/20/2024 |
| A17.1-2016 : Elevators | 2.31 - Relief Valves | 8.6.5.14.1 | Yes | No | The relief valve shall be tested. The pressure monitor was not working, so relief pressure could not be verified. | 7/23/2025 |
| A17.1-2016 : Elevators | 2.37 - Pressure Switch | 3.26.8 | Yes | No | The low pressure switch shall be tested. This test could not be completed because the pressure monitor was not working. | 7/23/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 3.26.10 | Yes | No | The auxiliary power lowering operation shall be functional. | 7/23/2025 |