Inspection
Inspection Details
Equipment ID
12831
12831
Inspection Date
7/23/2024
7/23/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kevin Hecht
Kevin Hecht
Mechanic Name
Bradley Tramel
Bradley Tramel
Relief Valve Pressure
340
340
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
14
14
External ID
eae91d10-9009-4940-aa03-f794547a6132
eae91d10-9009-4940-aa03-f794547a6132
Location
Summit Lofts
630 Emerson, Creve Coeur, MO
Phone: (314) 567-1910
630 Emerson, Creve Coeur, MO
Phone: (314) 567-1910
Owner
Attn: Summit Lofts Condo Association c/o O'Conner Management
Summit Lofts Condo Association c/o O'Conner Management
3516 Greenwood Blvd, St. Louis, MO 63131
Phone: (314) 646-7900
Summit Lofts Condo Association c/o O'Conner Management
3516 Greenwood Blvd, St. Louis, MO 63131
Phone: (314) 646-7900
Billing
Attn: Jamie Behrmann
Rodemyer-Christel, Inc.
3630 Grandel Sq, St. Louis, MO 63018
Phone: (000) 000-0000
Email: jbehrmann@rcirealty.com
Rodemyer-Christel, Inc.
3630 Grandel Sq, St. Louis, MO 63018
Phone: (000) 000-0000
Email: jbehrmann@rcirealty.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 11/21/2023 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | An ABC type fire extinguisher with a current test tag shall be provided in the machine room convenient to the access door. | 11/21/2023 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | 11/21/2023 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 11/21/2023 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | The pit shall be kept clean. Clean the pit. | 11/21/2023 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1001.2(b)(5) | No | No | The top of car shall be cleaned. | 11/21/2023 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 11/21/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 11/21/2023 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1 with identification of the person(s) that performed the operation, and the date shall be available on-site. | 11/21/2023 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | 11/21/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.7 Record of Oil Usage | No | No | A written record shall be kept of the quantity of hydraulic fluid added to the system and emptied from leakage collection containers and pans. The written record shall be kept in the machine room. | 11/21/2023 |
| A17.1-1996 : Elevators | 2.14 - Code data plate | 215 | No | No | A code data plate is required and shall be provided in plain view, securely attached to each main line disconnect or controller. | 11/21/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | The pit shall be kept free of dirt and rubbish. | 11/21/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | The car top shall be kept free of dirt. | 11/21/2023 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2b (Clean Machine Room) | No | No | The machine room shall be kept free of dirt and rubbish. | 11/21/2023 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car telephone shall be operational. | 6/8/2023 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | The fire extinguisher is out of date. | 11/21/2023 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | The pit needs to be kept clean. | 11/21/2023 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency phone is not working. | 7/23/2024 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2b (Clean Machine Room) | No | No | The machine room needs to be cleaned. | 11/21/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | There is no state operating certificate in the machine room. | 11/21/2023 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2c (Clean Car Tops) | No | No | Top of car needs to be cleaned. | 11/21/2023 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 102.4 | No | No | Machine room ventilation fan is not working. | 8/12/2024 |
| A17.1-1996 : Elevators | 1.2 - Stop switches | 210.2(e) | Yes | No | Emergency stop switch on car top is broken and needs to be repaired. | 7/31/2026 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 102.4 | No | No | Machine room ventilation fan is not working. | 7/31/2026 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 101.5b | No | No | Exhaust fan in machine room shall work. |