Inspection
Inspection Details
Equipment ID
25942
25942
Inspection Date
7/19/2024
7/19/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Brenton Lane
Brenton Lane
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
15F/16R
15F/16R
External ID
258a4afb-6408-49d8-817d-3ad5f8420be7
258a4afb-6408-49d8-817d-3ad5f8420be7
Location
21c Museum Hotel
1528 Locust St, St. Louis, MO
Phone: (314) 781-8000
1528 Locust St, St. Louis, MO
Phone: (314) 781-8000
Owner
Attn: Locust Street Property 1 STL, LLC
Locust Street Property 1 STL, LLC
1528 Locust St, St. Louis, MO 63103
Phone: (314) 781-8000
Email: boverbaugh@russellco.com
Locust Street Property 1 STL, LLC
1528 Locust St, St. Louis, MO 63103
Phone: (314) 781-8000
Email: boverbaugh@russellco.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Acceptance testing is incomplete. The following items still need to be tested and recorded: Slide, pull out/pull thru, governor electrical & mechanical speeds, door closing pressure, ring & string, fire alarm initiating device testing, emergency power. | 5/3/2023 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | ARU/Battery pack switch missing in disconnect. | 5/3/2023 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | Yes | No | Install all missing covers in machine room. | 5/3/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | Yes | No | Main and lighting disconnect shall be labeled. | 5/3/2023 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2 Phase I Operation Recall by Initiating Device | Yes | Yes | The following fire service devices failed to recall elevator. Machine room smoke, top of hoistway smoke, and all heat detectors (not tested). | 5/3/2023 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | Yes | No | 2.3.3 - Top of machine space (hoistway) lighting and outlet shall work. | 5/3/2023 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 | Yes | No | Pit light switch is not accessible from landing due to obstructions and location. | 5/3/2023 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2 Phase I Operation Recall by Initiating Device | Yes | Yes | Top of hoistway smoke needs to be reprogrammed. | 5/4/2023 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2 Phase I Operation Recall by Initiating Device | Yes | Yes | All heat detectors shall be tested. | 5/4/2023 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 12/4/2025 |
| A17.1-2016 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Room and Machinery Space | No | No | Articles or materials not necessary for the maintenance or operation of the elevator shall not be stored in the machine room. | 12/4/2025 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | Yes | No | Front door open button is not functioning on Phase 2 fire service. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Testing not complete: The following items still need to be tested/inspected: car door switch and restrictor, governor, safeties, unintended movement, emergency power and door closing force. |