Inspection
Inspection Details
Equipment ID
11496
Inspection Date
7/25/2024
Inspection Type
Annual Inspection
Inspector Name
Cynthia "CJ" Brady
Mechanic Name
Phillip Moise, Jr.
Relief Valve Pressure
460
Slide
NA
Governor Rope Pull
NA
Door Closing Force
15F/15R
External ID
33acce81-1a2e-4f05-acfc-cc99b879443a
Location
Glen Ridge Elementary
7447 Wellington Way, Clayton, MO
Phone: (314) 854-6950
Owner
Attn: Jim Brennell
Clayton School District
2 Mark Twain Cir, Clayton, MO 63105
Phone: (000) 000-0000
Email: deborahsperruzza@claytonschools.net
Violations
|
Code
|
Item
|
Section
|
Reinspection
|
Red Tag
|
Reason For Violation
|
Fixed Date
|
|
conversion
|
conversion
|
n/a
|
No
|
No
|
Cab ceiling light diffusers are missing and shall be re-installed.
|
11/11/2019
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
No
|
No
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
8/27/2021
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
No
|
No
|
Articles or materials not necessary for the maintenance or operation of the elevator shall not be stored in the machine room.
|
8/27/2021
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
The emergency phone needs to be reprogramed to be code compliant. A two-way communications means between the car and a location staffed by authorized personnel shall be provided.
|
7/21/2023
|
|
MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)4 (Re-Inspection)
|
Yes
|
No
|
Elevator did not pass the 15 minute static test. Take corrective action as needed. Elevator turned off by maintenance company.
|
7/21/2023
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
There is no state operating certificate in machine room.
|
9/21/2023
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
Yes
|
No
|
The in car emergency lights shall be operational.
|
7/22/2025
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
The in car emergency phone shall be operational.
|
7/22/2025
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)1
|
No
|
No
|
Non-elevator related items shall not be stored in Machine Room.
|
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)1
|
No
|
No
|
Water is accumulating on the machine room floor, around pump unit . Creates a dangerous situation for working on controller
|
|