Inspection
Inspection Details
Equipment ID
220
220
Inspection Date
8/5/2024
8/5/2024
Inspection Type
Reinspection
Reinspection
Inspector Name
James VanZant
James VanZant
Mechanic Name
Jeremiah Dugger
Jeremiah Dugger
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
22
22
External ID
ad39e565-57b5-4dfb-af9f-a68d13ed2920
ad39e565-57b5-4dfb-af9f-a68d13ed2920
Location
South Tower
770 SOUTH AVE, SPRINGFIELD, MO
Phone: (417) 866-4329
770 SOUTH AVE, SPRINGFIELD, MO
Phone: (417) 866-4329
Owner
Attn: Chuck Hicks
Springfield Housing Authority
421 W Madison St, Springfield, MO 65806
Phone: (000) 000-0000
Email: chicks@hasproperties.org
Springfield Housing Authority
421 W Madison St, Springfield, MO 65806
Phone: (000) 000-0000
Email: chicks@hasproperties.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | 1/5/21: Car Door restrictor shall work {front and rear}. (REINSPECTION REQUIRED) | 8/11/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | 1/5/21: Car Door restrictor shall work {front and rear}. (REINSPECTION REQUIRED) | 8/11/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | :Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) including Wiring Diagrams, Oil loss log and Fire service testing log, recorded monthly. | 5/3/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Car Door restrictor shall work. Front and Rear. | 3/30/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | H(8) Replace missing electrical box cover. | 5/3/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | H(5) Machine room lighting needs to be repaired | 5/3/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (2)(C) Re-Inspection Required to Enforce. | Yes | No | TESTING INCOMPLETE. MUST RETURN TO COMPLETE. Required within 30days | 3/30/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Car Door restrictor shall work. Front and Rear. | 3/30/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (2)(C) Re-Inspection Required to Enforce. | Yes | No | TESTING INCOMPLETE. MUST RETURN TO COMPLETE. Required within 30days | 3/30/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | 2-way communication device shall give proper location message, no Location message given. (REINSPECTION > 14days) | 11/17/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Key Switch bezel missing in COP | 11/29/2022 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | Remove/attach styrofoam insulation board at top rear of Hoistway(covering exterior ventilation vent). Currently just wedged behind piping, about to fall. | 11/29/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | G(1)/A17.1-2016:8.6.1.2.1(a)/2.40 Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) including Wiring Diagrams, Oil log &Fire service log, recorded monthly. | 11/29/2022 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Car hoist ropes undersized, replace per code | 8/5/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Provide onsite MCP | 6/3/2024 |