Inspection
Inspection Details
Equipment ID
8678
8678
Inspection Date
8/1/2024
8/1/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Brant Willtrout
Brant Willtrout
Relief Valve Pressure
370
370
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
20
20
External ID
f728ebe1-f584-4fb3-a615-6e749ece5336
f728ebe1-f584-4fb3-a615-6e749ece5336
Location
Cambridge Court Condos
917 Claytonbrook Dr, Ballwin, MO
Phone: (636) 227-0012
917 Claytonbrook Dr, Ballwin, MO
Phone: (636) 227-0012
Owner
Attn: Kathleen Peick
Cambridge Court Condos c/o Community Property Management
242 Old Sulphur Springs Rd, Manchester, MO 63021
Phone: (636) 227-8688
Email: kathleen@cpmgateway.com
Cambridge Court Condos c/o Community Property Management
242 Old Sulphur Springs Rd, Manchester, MO 63021
Phone: (636) 227-8688
Email: kathleen@cpmgateway.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 9/22/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (2)(C) Re-Inspection Required to Enforce. | Yes | No | Possible single bottom jack. If the installation is determined to be a single bottom type, the jack shall be replaced or have a governor with safeties installed or a plunger gripper installed. Documentation shall be kept on-site at all time and shall be provided to the state. | 9/6/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 10/31/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | Yes | No | The hydraulic tank drip pan has an excessive amount of oil, it shall be cleaned. | 9/6/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (2)(C) Re-Inspection Required to Enforce. | Yes | No | Possible single bottom jack. If the installation is determined to be a single bottom type, the jack shall be replaced or have a governor with safeties installed or a plunger gripper installed. Documentation shall be kept on-site at all time and shall be provided to the state. | 8/1/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | Yes | No | The hydraulic tank drip pan has an excessive amount of oil, it shall be cleaned. | 8/1/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Compliant/Required documentation shall be kept in the equipment room (neat/organized) including MCP, wiring diagrams, PM log, callback log, oil log, and evacuation procedures. Fire service log to be recorded monthly | 12/4/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | Yes | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | 8/1/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Door safety edge is working intermittently. Take corrective action as needed. | 8/1/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | Yes | No | Pit shall be kept dry. Remove rust from pit equipment and repair or replace as needed. Apply rust prevention treatment to all pit steel and investigate/repair water leak. | 8/1/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | Yes | No | Pit sump not working. Repair or replace as needed. | 8/1/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Cab lighting breaker not labeled and could not be found by mechanic. Location info shall be labeled on machine room. | 8/1/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (2)(C) Re-Inspection Required to Enforce. | Yes | No | Possible single bottom jack. If the installation is determined to be a single bottom type, the jack shall be replaced or have a governor with safeties installed or a plunger gripper installed. Documentation shall be kept on-site at all time and shall be provided to the state. There is no documentation in the machine room and jack head is 1973 Otis Cast head. All violations are repeat violations from previous years and the AHJ requires that all violations must be re-inspected. | 12/4/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | Yes | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. All violations are repeat violations from previous years and the AHJ requires that all violations must be re-inspected. | 12/4/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Door safety edge is working intermittently. Take corrective action as needed. All violations are repeat violations from previous years and the AHJ requires that all violations must be re-inspected. | 12/4/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | Yes | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. All violations are repeat violations from previous years and the AHJ requires that all violations must be re-inspected. | 12/4/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | Yes | No | Pit shall be kept dry. Remove rust from pit equipment and repair or replace as needed. Apply rust prevention treatment to all pit steel and investigate/repair water leak. All violations are repeat violations from previous years and the AHJ requires that all violations must be re-inspected. | 12/4/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | Yes | No | Pit sump not working. Repair or replace as needed. All violations are repeat violations from previous years and the AHJ requires that all violations must be re-inspected. | 12/4/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Cab lighting breaker not labeled and could not be found by mechanic. Location info shall be labeled on machine room. All violations are repeat violations from previous years and the AHJ requires that all violations must be re-inspected. | 12/4/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (2)(C) Re-Inspection Required to Enforce. | Yes | No | Need to determine if this unit has a single bottom jack. If it does it is required to be replaced or gobernor with safties installed or a plunger gripper on the unit. Ref: 8.6.5.8, A 17.2 - 5.11 memorandum froom the State of Missorui effective May 30, 2007, No documentation provided in the machine room. Jack head is 1973 OTIS CAST HEAD. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | Yes | No | Compliant/Required documentation shall be kept in the equipment room (neat/organized) including MCP, wiring diagrams, PM log, callback log, oil log, and evacuation procedures. Fire service log to be recorded monthly. (last documented update was 9/2023, must be updated on every visit) | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | Yes | No | Machine room fire extinguisher shall have current monthly/annual test tag. No extinguisher in toom or immediately adjacent to the door. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Yes | No | Door safety edge working intermittenly. | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | Yes | No | Pit shall be kept dry. Remove rust from pit equipment, repair/replace as needed, apply rust prevention treatment to all pit steel, investigate/repair water leak. | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | Yes | No | Cab lighting breaker not labeled an could not found by mechanic. Location info shall be labeled in machine room (lighting tested by alternate means) |