Inspection
Inspection Details
Equipment ID
19083
19083
Inspection Date
8/6/2024
8/6/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Bradley Rasnake
Bradley Rasnake
Mechanic Name
Ronald Hogue, Jr
Ronald Hogue, Jr
Relief Valve Pressure
560
560
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
20 / 12
20 / 12
External ID
f371344f-1bbe-4d0b-8bd3-fa380fa52c00
f371344f-1bbe-4d0b-8bd3-fa380fa52c00
Location
2200 Gravois, LLC
2200 Gravois Ave, St. Louis, MO
Phone: (314) 517-0965
2200 Gravois Ave, St. Louis, MO
Phone: (314) 517-0965
Owner
Attn: 2200 Gravois, LLC
2200 Gravois, LLC
2200 Gravois Ave, Ste 100, St. Louis, MO 63104
Phone: (314) 517-0965
Email: 2200gravois@gmail.com
2200 Gravois, LLC
2200 Gravois Ave, Ste 100, St. Louis, MO 63104
Phone: (314) 517-0965
Email: 2200gravois@gmail.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | No | No | The machine room GFCI receptacle was not operational on the day of inspection. Repair the receptacle for maintenance and emergency personnel. | 10/16/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 8.11.2.1.2(f) | No | No | The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller. | 10/16/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | The elevator pit floor is covered in saturated oil dry. The elevator pit shall be kept clean and dry. | 10/16/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.11.2.1.1(e) Car Lighting | No | No | A light fixture inside the elevator is not operational and shall be repaired. | 10/16/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.1 - Door Re-opening device | 8.6.4.13.1(c) Door Reopening Devices | No | No | Repair front door safety edge. | 7/20/2021 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | No | No | OSV is not sealed and must have a cat 5 weight weight test performed within 90 days or less | 11/17/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.35 - Supply Line and Shutoff Valve | 3.19 | Yes | Yes | Pipe coming out of machine room is leaking excessively, must be replaced. Red tagged, Re-inspection required | 9/19/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4 | No | No | 110 disconnect rusting through, shall be replaced | 9/27/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4 | No | No | 110 disconnect rusting through, needs to be replaced | 9/15/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not working. Re-inspection required | 9/20/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4 | No | No | 110 disconnect is rusting through, needs to be replaced | 9/15/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone in elevator cab does not work. Phone line has no power. Repair. Reinspect within 30 days. |