Inspection
Inspection Details
Equipment ID
21049
21049
Inspection Date
8/8/2024
8/8/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
300
300
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
18
18
External ID
77f03e8a-6793-46b4-b542-4c67b0fd57fa
77f03e8a-6793-46b4-b542-4c67b0fd57fa
Location
Fresh Properties
800 Lumiere Place Blvd, St. Louis, MO
Phone: (618) 482-8712
Alt Phone: (314) 575-4633
800 Lumiere Place Blvd, St. Louis, MO
Phone: (618) 482-8712
Alt Phone: (314) 575-4633
Owner
Attn: Champika Lindskog
Pershing Investment LLC
4954 W Pine Blvd, #503, St. Louis, MO 63108
Phone: (314) 803-2024
Email: parkstationmgr@att.net
Pershing Investment LLC
4954 W Pine Blvd, #503, St. Louis, MO 63108
Phone: (314) 803-2024
Email: parkstationmgr@att.net
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The elevator ADA telephone inside the elevator is not working properly. Check and repair the phone line of this phone for proper operation and passenger safety. Reinspection required. | 6/1/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | The fire extinguisher in the machine room shall be serviced, the last annual service tag indicates it was serviced in 2018 | 4/30/2021 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | The elevator hoistway shall be fully enclosed. Inside the hoistway drywall has become dislodged due to flooding that shall be repaired and the elevator shaft shall retain its hoistway fire rating. | 4/30/2021 |
| MO Minimum : Elevators | (O) - Existing Hydraulic Elevators | (O)4 | No | No | The belts on the hydraulic pump motor are cracked and worn unevenly. Replace belts for a smooth operation of pump to motor. | 4/30/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. Second Notice | 3/2/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.27 - Crosshead data plate | 2.16.3 | Yes | No | A cross head data plate shall be provided. | 3/8/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | Yes | No | There is an unknown pipe protruding from the pit floor. The pipe shall be removed or a variance applied for. | 3/8/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4 | Yes | No | Label the disconnects with the location, source, and breaker numbers of the panel from which it is fed. | 3/8/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | Yes | No | A monthly fire service testing log shall be provided. | 3/8/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | Yes | No | All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 3/8/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall operate properly. | 3/8/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Yes | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | 3/8/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | MAchine room shall have proper fire extinguisher and shall have current monthly/annual test tag. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The up to date State operating certificate must be displayed. |