Inspection
Inspection Details
Equipment ID
14499
14499
Inspection Date
8/14/2024
8/14/2024
Inspection Type
Special Inspection
Special Inspection
Inspector Name
Melvin Barks Jr.
Melvin Barks Jr.
Mechanic Name
Relief Valve Pressure
N/A
N/A
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
N/A
N/A
External ID
257e5a3e-8c1c-4321-a799-e90bddb58382
257e5a3e-8c1c-4321-a799-e90bddb58382
Location
Terra Cotta Parking Garage
410 N 16th St, St. Louis, MO
Phone: (314) 621-6750
410 N 16th St, St. Louis, MO
Phone: (314) 621-6750
Owner
Attn: Jessie Blaha-Reid
Terra Cotta Garage c/o Sentry Management
9666 Olive Blvd, Ste 116, St. Louis, MO 63132
Phone: (314) 994-7440
Email: jblaha@sentrymgt.com
Terra Cotta Garage c/o Sentry Management
9666 Olive Blvd, Ste 116, St. Louis, MO 63132
Phone: (314) 994-7440
Email: jblaha@sentrymgt.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | clean elevator pit | 9/21/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall work. | 8/16/2019 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Remove water and oil from pit. | 1/28/2021 |
| A17.1-1996 : Elevators | 1.8 - Door closing force | 1001.2(a)(8) | Yes | No | The door closing force shall not exceed 30 lbs. | 10/12/2021 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | The pit shall be kept clean. | 11/29/2023 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 11/29/2023 |
| A17.1-1996 : Elevators | 1.8 - Door closing force | 1001.2(a)(8) | Yes | No | The door closing pressure still exceeds 30 lbs. The door is timing out and stalling. Take corrective action as needed. | 11/29/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces | Yes | No | Remove all non elevator related items from machine room. Re-inspection required | 5/5/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of current state operating certificate needs to be properly displayed in machine room | 11/29/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit needs to be cleaned | 11/29/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | pit light shall work | 11/29/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | A written Maintenance control program shall be kept on site for each elevator | 11/29/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Cartop light bulb is burned out. replace same | 11/29/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light and alarm shall work | 8/4/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Elevator machine room is not to be used for storage of non elevator related materials and equipment. Remove same | 11/29/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Repair fire service phase 2 key switch. Not Red Tagged. 14 days to correct violation. | 12/20/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Fire service phase 2 operation shall be tested. | 12/20/2024 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2c (Clean Car Tops) | No | No | Clean cartop. | 6/10/2025 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | Fire service testing shall be documented monthly. | 6/10/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | New fire alarm panel in the machine room is not allowed. Either relocate outside of the room or state variance from elevator board shall be applied to allow installation. | 6/10/2025 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | Pit shall be kept clean. | 6/10/2025 |