Inspection
Inspection Details
Equipment ID
22680
22680
Inspection Date
8/15/2024
8/15/2024
Inspection Type
Alteration
Alteration
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Michael Wallis
Michael Wallis
Relief Valve Pressure
Na
Na
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
Na
Na
External ID
201e90f6-8acf-40dc-91b2-f1ce3cba753b
201e90f6-8acf-40dc-91b2-f1ce3cba753b
Location
Whole Foods
4577 West Pine Blvd, St. Louis, MO
Phone: (314) 474-7300
Email: shawn.milford@wholefoods.com
4577 West Pine Blvd, St. Louis, MO
Phone: (314) 474-7300
Email: shawn.milford@wholefoods.com
Owner
Attn: The Dedicated Orion, LP
The Dedicated Orion, LP
4567 W Pine Blvd, St. Louis, MO 63108
Phone: (000) 000-0000
Email: ormanager@theorioncwe.com
The Dedicated Orion, LP
4567 W Pine Blvd, St. Louis, MO 63108
Phone: (000) 000-0000
Email: ormanager@theorioncwe.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Repair Basement Floor Hall sill trip Hazard | 7/9/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.6.4.11 | Yes | No | Counterweights bottom out before car reaches its final limit. Repair | 12/16/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Written maintenance control program shall be kept on site for each elevator. | 9/15/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.13 - Windows, projections, recesses, and setbacks | 8.11.2.1.3(s) | No | No | Sill guards are missing at the bottom of all hoistway door landing sills. Guards shall be the length of the car leveling zone, plus 3 inches, and be beveled at an angle between 60 and 75 degrees. | 9/15/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Emergency generator testing shall be performed. Re-inspection required | 2/3/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Access to the elevator disconnects shall be unobstructed | 9/15/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The door to the elevator disconnects shall be self closing & self locking | 9/15/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | No flammable materials are to be stored in the elevator disconnect room | 9/15/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.13 - Windows, projections, recesses, and setbacks | 8.11.2.1.3(s) | No | No | Sill guards are missing at the bottom of all hoistway door landing sills. Guards shall be the length of the car leveling zone, plus 3 inches, and be beveled at an angle between 60 and 75 degrees. Previous violations from past years. | 9/15/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Emergency generator testing shall be performed. Re-inspection required.Previous violations from past years. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.4 - Sills and car floor | 2.11.11.1 | No | No | Repair Bottom Floor Trip hazard at hall sill. Previous violation from past years. | 9/15/2025 |