Inspection
Inspection Details
Equipment ID
19056
19056
Inspection Date
8/9/2024
8/9/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Ledden
Michael Ledden
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
290
290
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
17
17
External ID
9279381a-9cc6-4b29-8a6a-ca15d300fa5d
9279381a-9cc6-4b29-8a6a-ca15d300fa5d
Location
416 N. 23rd LLC
414 N 23rd St, St. Louis, MO
Phone: (314) 806-3915
414 N 23rd St, St. Louis, MO
Phone: (314) 806-3915
Owner
Attn: Rob Maltby
AHM Management
3101 Arsenal St, St. Louis, MO 63118
Phone: (314) 257-0001
Email: Rob@ahmre.com
AHM Management
3101 Arsenal St, St. Louis, MO 63118
Phone: (314) 257-0001
Email: Rob@ahmre.com
Billing
Attn: Matthew Ryffel
AHM Management
2223 Locust, St. Louis, MO 63103
Phone: (314) 257-0001
Email: MRyffel@AHMRE.com
AHM Management
2223 Locust, St. Louis, MO 63103
Phone: (314) 257-0001
Email: MRyffel@AHMRE.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.37 Pressure switch | 306.14 Pressure switch | Yes | No | Where the top of the cylinder is installed above the top of the storage tank, a pressure switch shall be provided according to A17.1 - 3.26.8 | 11/20/2020 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 9/15/2021 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. | 9/15/2021 |
| A17.1-1996 : Elevators | 2.14 - Code data plate | 1200.6 | No | No | Install a code data plate. It shall read: A17.1-1996 | 9/15/2021 |
| A17.1-1996 : Elevators | 2.11 - Disconnecting Means and Control | 1001.2(b)(11) | No | No | The disconnect located in the machine room shall be provided with a sign to identify the location of the supply side overcurrent protective device. | 9/15/2021 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Clean the pit of oil, dirt, and debris. | 9/15/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The hall call box located on the 1st floor landing is pulling away from the wall. Take corrective action as needed. | 9/15/2021 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | 11/22/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 11/22/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Each floor shall have "In Case of Fire Use Stairs" signage. | 11/22/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational and code compliant. | 11/15/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | "In Case of Fire" signage is required at each floor. (On order per building contact) | 12/7/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall be operational. | 9/5/2024 |