Inspection
Inspection Details
Equipment ID
16071
16071
Inspection Date
7/24/2024
7/24/2024
Inspection Type
Temporary Certificate Inspection
Temporary Certificate Inspection
Inspector Name
Sean Carmody
Sean Carmody
Mechanic Name
Mark Dolan
Mark Dolan
Relief Valve Pressure
NA
NA
Slide
24"
24"
Governor Rope Pull
30/400
30/400
Door Closing Force
22
22
External ID
ba8b249d-7c6a-4048-a91c-ad600213281d
ba8b249d-7c6a-4048-a91c-ad600213281d
Location
The New Jefferson Arms
415 N Tucker Blvd, St. Louis, MO
Phone: (314) 436-4600
415 N Tucker Blvd, St. Louis, MO
Phone: (314) 436-4600
Owner
Attn: The New Jefferson Arms
The New Jefferson Arms-Bldg is vacant
415 N TUCKER BLVD, SAINT LOUIS, MO 63101-1129
The New Jefferson Arms-Bldg is vacant
415 N TUCKER BLVD, SAINT LOUIS, MO 63101-1129
Billing
Attn: The New Jefferson Arms
Barry Cohen
415 N TUCKER BLVD, SAINT LOUIS, MO 63101-1129
Barry Cohen
415 N TUCKER BLVD, SAINT LOUIS, MO 63101-1129
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 2.1 | Yes | No | Hostway shall be encolsed with a 2 hr fire rated construction throughout. Penetrations exist throughout hoistway and shall be patched and rated. | |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | Yes | No | Pit and Car top need cleaned of construction dust and debris. | |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.9 Elevator Corridor Call Station Pictograph | Yes | No | "In Case of Fire" signage shall be provided in hallway at each landing | |
| A17.1-2016 : Elevators | 1.4 - Sills and car floor | 2.11.11.1 | Yes | No | Car Floor to car sill has a 1/2" lip and presents a trip hazard. Bevel or level to removed trip hazard. | |
| A17.1-2016 : Elevators | 11.1 - Access to Machine Room/Machinery Space/Control Room/Control Space | 2.7.3 | Yes | No | Machine Room and Secondary Machine room shall have a self closing and self locking door | |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.7.9.1 | Yes | No | Old and unused wiring and light switches in machine room shall be removed. | |
| A17.1-2016 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Room and Machinery Space | Yes | No | Machine room needs cleaned of construction dust and debris. | |
| A17.1-2016 : Elevators | 2.6 - Ventilation | 2.7.9.2 | Yes | No | Air conditioning shall be installed and function to keep controllers at manufacturers recommended temperature. | |
| A17.1-2016 : Elevators | 6.5 -Acceptance Checklist for Firefighters' Service (ASME A17.1-2000 and CSA B44-00): Automatic Elevators | 2.27.3 | Yes | Yes | Fire alarm initiating device (smoke) on second floor shall recall elevator to main fire floor (floor 1) | |
| A17.1-2016 : Elevators | 1.4 - Sills and car floor | 2.11.11.1 | Yes | No | Hall Sill to hall floor presents a trip hazard on floors M, 2, 4, 6, 9, 20, 11, 12. Hall floor shall be level with hall sill. | |
| A17.1-2016 : Elevators | 3.27 - Crosshead Data Plate and Rope Data Tags | 2.20.2 | Yes | No | Crosshead data plate shall be provided and engraved | |
| A17.1-2016 : Elevators | 4.12 - Standby power selection switch | 2.27.2 | Yes | No | Emergency Power / Standby power shall be tested |