Inspection
Inspection Details
Equipment ID
80
80
Inspection Date
8/16/2024
8/16/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Dennis Smith
Dennis Smith
Mechanic Name
Dennis Smith
Dennis Smith
Relief Valve Pressure
490
490
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
27
27
External ID
8ab9a953-9f68-418b-8ace-47d23188201f
8ab9a953-9f68-418b-8ace-47d23188201f
Location
Mosaic Medical Center-Maryville
2016 S Main St, Maryville, MO
Phone: (660) 562-2600
2016 S Main St, Maryville, MO
Phone: (660) 562-2600
Owner
Attn: Ryan Rush, MHA
Mosaic Medical Center-Maryville
2016 S Main St, Maryville, MO 64468
Phone: (816) 271-6816
Alt Phone: (816) 646-3013
Email: Ryan.Rush@mymlc.com
Mosaic Medical Center-Maryville
2016 S Main St, Maryville, MO 64468
Phone: (816) 271-6816
Alt Phone: (816) 646-3013
Email: Ryan.Rush@mymlc.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate | 9/30/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 | No | No | Provide lighting in machine room. Existing feed for machine lights has no electrical power | 2/22/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)6 | No | No | Label machine room equipment with identification that corresponds to identification inside the elevator and the car crosshead. | 11/16/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Identify inside of hoistway doors with a numeral corresponding to landing floor. | 11/16/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Perform emergency standby operation with an inspector present. | 8/24/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Provide "Elevator Emergency Power" signal at the lobby of the designated landing. | 9/8/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate | 11/21/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.2 (Re-Inspection) | Yes | No | Replace pit sprinkler head with sidewall sprinkler head located within 24 inches of pit floor | 11/21/2023 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.5.14.3(f) | Yes | No | Test emergency power operation with inspector present | 11/21/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | No | No | REPAIR PIT LIGHTING | 10/21/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.8 - Door closing force | 2.13.4.2.3 | Yes | No | FRONT DOOR TORQUE IS >30lbs | 1/16/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.5 - Normal terminal stopping device | 2.26.2 | Yes | No | DOWN LIMIT DID NOT WORK | 1/16/2026 |