Inspection
Inspection Details
Equipment ID
11828
11828
Inspection Date
8/16/2024
8/16/2024
Inspection Type
Reinspection
Reinspection
Inspector Name
Dennis Smith
Dennis Smith
Mechanic Name
Relief Valve Pressure
N/A
N/A
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
N/A
N/A
External ID
65e1516c-cb98-4a86-b302-43b0eef414e7
65e1516c-cb98-4a86-b302-43b0eef414e7
Location
Stoney Creek Inn
1201 N Woodbine Rd, St. Joseph, MO
Phone: (816) 901-9600
Email: kerra.flatt@stoneycreekhotels.com
1201 N Woodbine Rd, St. Joseph, MO
Phone: (816) 901-9600
Email: kerra.flatt@stoneycreekhotels.com
Owner
Attn: Kerra Flatt
Stoney Creek Inn
1201 N Woodbine Rd, St. Joseph, MO 64506
Phone: (816) 901-9600
Email: kerra.flatt@stoneycreekhotels.com
Stoney Creek Inn
1201 N Woodbine Rd, St. Joseph, MO 64506
Phone: (816) 901-9600
Email: kerra.flatt@stoneycreekhotels.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | Test firefighters operation monthly and provide log in machine room. | 9/22/2020 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3b | No | No | Machine room access door needs to be self-closing. | 9/22/2020 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | No | No | Post firefighters instructions next to hall fire keyswitch. | 9/22/2020 |
| A17.1-1996 : Elevators | 2.14 - Code data plate | 215 | No | No | Post code data plate on controller or mainline disconnect. | 9/22/2020 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Post emergency evacuation of passengers form inside machine room. | 9/22/2020 |
| A17.1-2016 : Elevators | 2.4 - Machine space | 8.6.4.8 Machine Room and Machinery Space | No | No | Remove non elevator related material from machine room. Remove trash, rags and flammable items. | 9/22/2020 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide test tag for record of annual pressure relief test. | 9/22/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate | 1/5/2022 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | No | No | Post firefighter instructions next to hall fire keyswitch | 11/8/2021 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 1001.2(a)(18) | Yes | No | Car door restrictor does not function | 1/5/2022 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | Test and log firefighter operation monthly | 11/8/2021 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Install pit collection containers for cylinder drain lines and remove waste oil from pit floor. | 11/8/2021 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | Emergency light does not illuminate when normal power for car lights is off. | 6/15/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | REPAIR HOLE IN MACHINE ROOM CELING WHERE THE SHEETROCK WAS REMOVED TO DO A REPAIR ABOVE THE CELING | 8/12/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)7 | No | No | DOOR CLOSING FORCE IS >30 LBS | 8/12/2024 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone and bell do not work | |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | No | No | Phase II not working |