Inspection
Inspection Details
Equipment ID
16124
16124
Inspection Date
8/16/2024
8/16/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kenin Lynes
Kenin Lynes
Mechanic Name
Brant Willtrout
Brant Willtrout
Relief Valve Pressure
480
480
Slide
n/a
n/a
Governor Rope Pull
n/a
n/a
Door Closing Force
20
20
External ID
38f784a3-bba8-48f2-bce0-02f114f50f72
38f784a3-bba8-48f2-bce0-02f114f50f72
Location
Union Sara Apartments
4109 Enright Ave, St. Louis, MO
Phone: (314) 361-4750
4109 Enright Ave, St. Louis, MO
Phone: (314) 361-4750
Owner
Attn: Alice Thomas
Monroe Group
6875 E Evans Ave, Denver, CO 80224
Phone: (000) 000-0000
Email: athomas@monroegroup.com
Monroe Group
6875 E Evans Ave, Denver, CO 80224
Phone: (000) 000-0000
Email: athomas@monroegroup.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Door restrictor must be made operational | 10/20/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Need testing procedures included in the MCP | 5/12/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 5/12/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Pit needs to be cleaned | 5/12/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Repair machine room lighting | 5/12/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State certificate in machine room | 5/12/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Provide testing procedures in the MCP | 5/12/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Repair car gate light ray | 5/12/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean pit | 5/12/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Repair phone in car | 5/16/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency communication phone in car not working | 2/1/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service and document on log in machine room | 10/23/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | clean pit | 10/23/2023 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | Yes | No | Make door restrictor operable. | 6/3/2025 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | POST CURRENT STATE CERTIFICATE IN THE MACHINE ROOM | 8/4/2026 |
| A17.1-2016 : Elevators | 6.1 - Operation of elevators under fire and other emergency conditions (A17.1b-1973 through A17.1b-1980) | 8.6.11.1 Firefighters’ Emergency Operation | No | No | PERFORM MONTHLY FIRE SERVICE TEST AND DOCUMENT ON THE LOG POSTED IN THE MACHINE ROOM | 8/4/2026 |
| A17.1-2016 : Elevators | 6.1 - Operation of elevators under fire and other emergency conditions (A17.1b-1973 through A17.1b-1980) | 8.6.4.19.6 | Yes | Yes | Make repairs to Fire service operation, Red Tagged, /Reinspection required | 8/14/2026 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.11.1.3 Emergency Phone not workng Alarm Functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Phone inoperative | 8/14/2026 |