Inspection
Inspection Details
Equipment ID
12789
12789
Inspection Date
8/16/2024
8/16/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kenin Lynes
Kenin Lynes
Mechanic Name
Brant Willtrout
Brant Willtrout
Relief Valve Pressure
430
430
Slide
n/a
n/a
Governor Rope Pull
n/a
n/a
Door Closing Force
25
25
External ID
0981b121-f810-448f-8c91-776921e0a9da
0981b121-f810-448f-8c91-776921e0a9da
Location
Union Sarah 510 Demo Apts
4223 Enright Ave, St. Louis, MO
Phone: (314) 305-0786
4223 Enright Ave, St. Louis, MO
Phone: (314) 305-0786
Owner
Attn: Alice Thomas
Monroe Group
6875 E Evans Ave, Denver, CO 80224
Phone: (000) 000-0000
Email: athomas@monroegroup.com
Monroe Group
6875 E Evans Ave, Denver, CO 80224
Phone: (000) 000-0000
Email: athomas@monroegroup.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a | Yes | No | Remove oil trash from pit floor | 6/8/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 5/18/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Need testing procedures in the MCP | 5/18/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Pit needs to be cleaned | 5/18/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency phone not working | 9/7/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 5/18/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service and document on log in machine room | 10/23/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Repair machine room lights | 10/23/2023 |
| A17.1-2016 : Elevators | 2.33 - Tanks | 8.6.5.4 | No | No | Oil reservoir is low on oil. | 10/2/2024 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a | Yes | No | REMOVE WATER FROM THE PIT | 8/4/2026 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | POST CURRENT STATE CERTIFICATE IN THE MACHINE ROOM | 8/4/2026 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | PERFORM MONTHLY FIRE SERVICE TEST AND DOCUMENT ON THE LOG POSTED IN THE MACHINE ROOM | 8/4/2026 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | REPAIR THE PHONE IN THE CAR. REINSPECTION REQUIRED | 8/4/2026 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.11.1.3 Emergency Phone not workng Alarm Functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Repair Phone in Car | |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post Current Certificate in Machine Room | |
| A17.1-2016 : Elevators | 6.1 - Operation of elevators under fire and other emergency conditions (A17.1b-1973 through A17.1b-1980) | 8.6.4.19.6 | Yes | No | Perform Monthly Fire Service Test and Document on Log Sheet |