Inspection
Inspection Details
Equipment ID
2611
2611
Inspection Date
8/13/2024
8/13/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Raymond Stidham
Raymond Stidham
Mechanic Name
Matthew Trehal
Matthew Trehal
Relief Valve Pressure
440
440
Slide
Governor Rope Pull
Door Closing Force
19
19
External ID
ab3067ae-cd72-4950-84b1-02e28498071b
ab3067ae-cd72-4950-84b1-02e28498071b
Location
Crowder College- Neosho
601 Laclede Ave, Neosho, MO
Phone: (417) 455-5544
Email: TJAngel@crowder.edu
601 Laclede Ave, Neosho, MO
Phone: (417) 455-5544
Email: TJAngel@crowder.edu
Owner
Attn: Crowder
Crowder College- Neosho
601 Laclede Ave, Neosho, MO 64850
Phone: (000) 000-0000
Email: accountspayable@crowder.edu
Crowder College- Neosho
601 Laclede Ave, Neosho, MO 64850
Phone: (000) 000-0000
Email: accountspayable@crowder.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | telephone will not call out | 7/29/2018 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit Scavenger pump shall be removed | 4/27/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)6 | No | No | Detector edge wired to cab lighting circuit. Edge shall work independent of cab lighting. | 4/27/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | 2-way communication device shall work and give proper location. | 9/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.14 - Ventilation | 2.14.3.3 | No | No | Cab forced ventilation fan shall work | 4/27/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.14 - Ventilation | 2.14.2.3 | No | No | Cab fan Shall work | 4/27/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit Scavenger pump shall be removed | 9/10/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)6 | No | No | Detector edge wired to cab lighting circuit. Edge shall work independent of cab lighting. | 9/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.14 - Ventilation | 2.14.2.3 | No | No | Cab fan Shall work | 9/10/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Pit Scavenger pump shall be removed(2020&2021 vio) | 4/27/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.14 - Ventilation | 2.14.2.3 | No | No | Cab forced ventilation fan shall work, (2020&2021 vio) | 4/27/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Repair damaged Hoistway door guides, 3rd floor | 9/16/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | B(11)/1.6.1/ : 2-WAY COMMUNICATION DEVICE SHALL WORK. (Dials repeatedly, never connects) | 10/24/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Machine Room Fire Extinguisher has been removed from room, replace | 11/16/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit shall be kept dry. Remove rust from pit equipment , repaint, investigate/repair water leak | 11/16/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Current State Operating Permit shall be displayed in the Equipment Room in a non-combustible frame. (Cert on display expired 2019) | 11/16/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) including Wiring Diagrams, Oil log &Fire service log, recorded monthly. (Provided by Elev Co.) | 11/16/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | B(11)/1.6.1/ : 2-WAY COMMUNICATION DEVICE SHALL WORK. (Dials repeatedly, never connects) | 10/24/2022 |